| Plan Review Notes For Permit 16090458 |
| Permit Number |
16090458 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-19 16:03:11 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. | | | A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL | | | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION | | | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER | | | CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING | | | POWER DENSITY CHART TO SHOW COMPLIANCE. | | | | | | 2] FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER | | | OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM | | | OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR | | | A MAXIMUM OF 3% VOLTAGE DROP. | | | | | | 3] PROVIDE MANUFACTURE SPECS OF THE X-RAY MACHINE. FBC | | | 107 |
|