| Date |
Text |
| 2016-10-12 12:34:30 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 5TH EDITION |
| | |
| | 1. THIS STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA. THE SHELL WAS PERMITTED WITHOUT A CONCRETE FLOOR. |
| | PROVIDE THE PERMIT NUMBER FOR THE FLOOR FOR THIS UNIT, |
| | OR INCLUDE IN THIS SUBMITTAL. IF INCLUDED IN THIS |
| | PERMIT, A FORM BOARD SURVEY WITH ELEVATIONS OR |
| | ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR TO |
| | CONCRETE POUR. AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED PRIOR TO FINAL INSPECTION. |
| | |
| | 2. FBC 2014 ACCESSIBILITY 208.2.2, REHABILITATION |
| | FACILITIES AND OUTPATIENT PHYSICAL THERAPY FACILITIES |
| | HAVE ADDITIONAL ACCESSIBLE PARKING REQUIREMENTS. REVISE |
| | PLAN TO SHOW COMPLIANCE. |
| | |
| | 3. APPLICATION STATES SQUARE FOOT AREA IS 2500, PLAN |
| | SHOWS 1599, EXPLAIN AREA DISCREPANCY AND REVISE, FBC |
| | 107. |
| | |
| | 4. PLANS STATE THAT THIS IS AN EXISTING BUILDING, BUT |
| | THIS WAS PERMITTED AS A SHELL BUILDING, C.O. TO BE |
| | ISSUED UPON TENANT BUILDOUT. THIS PROJECT IS GOVERNED |
| | BY FBC BUILDING, NOT EXISTING BUILDING, REVISE. |
| | |
| | 5. STRUCTURAL NOTES, A0.03, SEE FBC 1603.1.4 AND REVISE |
| | WIND SPEED INFORMATION. |
| | |
| | 6. M2, RTU DETAIL REFERS TO STRUCTURAL FOR CURB DETAIL, |
| | PROVIDE, FBC1609. |
| | |
| | 7. VALUE ADJUSTMENT PER ICC TABLE WAS DONE, FBC 109. |
| | THE VALUE OF THE SHELL WAS DEDUCTED FROM THE VALUE IN |
| | THE ICC TABLE. |
| | |