| Plan Review Notes For Permit 16090453 |
| Permit Number |
16090453 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-09-22 07:36:17 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16090453 | | | 9/22/16 | | | | | | 1) PROVIDE RETURN AIR FROM BEDROOM #4- SECTION M1602 | | | FBC-RESIDENTIAL. | | | | | | 2) THE PLAN INDICATES 1180 CFMS AIR DISTRIBUTION AT THE | | | TWO TRUNK LINES, BUT ONLY 956 CFMS ARE SHOWN AT THE | | | BRANCH DUCTS AND DIFFUSERS- PLEASE CORRECT. | | | | | | 3) WHEN RESUBNITTING OLEASE NOTE TWO SETS OF PLANS ARE | | | REQUIRED PER SECTION 107.1 WPB AMENDMENTS TO THE FBC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|