| 2016-10-31 10:44:48 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | |
| | 1. COMMENTS FROM FIRST REVIEW HAVE NOT BEEN ADEQUATELY |
| | ADDRESSED. |
| | 2. APPLICANT HAS PROVIDED A FASTENER SCHEDULE WITH NO |
| | SUPPORTING CODE REFERENCE. THE FASTENER SCHEDULE SHOULD |
| | BE BASED ON THE DESIGN WIND LOAD OF THE EXTERIOR |
| | COMPONENT. |
| | 3. PROVIDE DESIGN WIND LOADS FOR SCREEN ENCLOSURE. |
| | 4. APPLICANT STAYES THE VALUE IS ESTIMATED AT LESS THAN |
| | $1,500.00. PLEASE PROVIDE A COPY OF A CONTRACT SIGNED |
| | BY THE OWNER OR A LIST OF MATERIALS AND ESTIMATED LABOR |
| | INCLUDING ANY RENTALS. |
| | 5. DESIGNER TO PRINT NAME AND SIGN PLANS. |
| | |
| | FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN |
| | PRESSURES PURSUANT TO FBC-R301.2. |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF |
| | THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND |
| | DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1. |
| | |
| | 2002.4 LOADS. |
| | STRUCTURAL MEMBERS SUPPORTING SCREENED ENCLOSURES SHALL |
| | BE DESIGNED FOR WIND IN BOTH OF TWO ORTHOGONAL |
| | DIRECTIONS USING THE PRESSURES GIVEN IN TABLE 2002.4. |
| | EACH PRIMARY MEMBER SHALL ALSO BE DESIGNED FOR A 300 |
| | POUND (1.33 KN) LOAD APPLIED VERTICALLY DOWNWARD ALONG |
| | ANY 1 FOOT (305 MM) OF ANY MEMBER, NOT OCCURRING |
| | SIMULTANEOUSLY WITH WIND LOAD. |
| | |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | 2. RISK CATEGORY. |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | VALUATION ? BASED ON THE MARSHALL-SWIFT VALUATION |
| | SERVICE YOUR STATED VALUE APPEARS LOW. |
| | THE STATED VALUATION IS TOO LOW FOR THE PROPOSED SCOPE |
| | OF WORK. |
| | THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| | CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION |
| | ACCORDINGLY. |
| | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE |
| | OWNER TO VERIFY VALUE. |
| | |
| | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION |
| | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), |
| | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL. |
| | |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |
| | |
| | |
| | |
| | |