| 2016-09-22 08:21:27 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16090425 |
| | ADD: 1914 MERRY PLACE UNIT 3 OF 3 |
| | CONT: WEST PALM BEACH HOUSING AUTHORITY |
| | TEL: 561-676-8442 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. SEPT. 22/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE (3) SEPARATE BUILDING PERMITS SUBMITTED |
| | AND ONLY (3) SETS OF PLANS WERE SUBMITTED. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | SECTION 107 SUBMITTAL DOCUMENTS. 107.1 SUBMITTAL |
| | DOCUMENTS CONSISTING OF CONSTRUCTION DOCUMENTS, |
| | GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED |
| | IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION. |
| | |
| | 2) SITE PLANS WILL NEED TO IDENTIFY NORTH AND WHICH |
| | UNITS ARE NORTH, SOUTH AND WEST AS INDICATED ON THE |
| | PERMIT APPLICATION. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 3) PLEASE DECLARE COMPLIANCE WITH 2014 FBC-B 503.1.2 |
| | BUILDINGS ON SAME LOT. TWO OR MORE BUILDINGS ON THE |
| | SAME LOT SHALL BE REGULATED AS SEPARATE BUILDINGS OR |
| | SHALL BE CONSIDERED AS PORTIONS OF ONE BUILDING IF THE |
| | BUILDING HEIGHT OF EACH BUILDING AND THE AGGREGATE |
| | BUILDING AREA OF THE BUILDINGS ARE WITHIN THE |
| | LIMITATIONS OF TABLE 503 AS MODIFIED BY SECTIONS 504 |
| | AND 506. THE PROVISIONS OF THIS CODE APPLICABLE TO THE |
| | AGGREGATE BUILDING SHALL BE APPLICABLE TO EACH |
| | BUILDING. |
| | |
| | 4) THERE IS A PLAN 11X17 OF THE 3 UNITS RAISED DECK, |
| | STAIRS, RAMP WITH HAND RAILS AND GUARDRAILS. NO ONE HAS |
| | TAKEN RESPONSIBILITY FOR THIS PLAN ? |
| | 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. |
| | |
| | 5) THERE IS A PLAN 11X17 OF THE 3 UNITS RAISED DECK, |
| | STAIRS, RAMP WITH HAND RAILS AND GUARDRAILS. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | (7) MEANS OF EGRESS |
| | STAIRS CONSTRUCTION/LOADING/GEOMETRY AND PROTECTION |
| | HAND RAILS/ GUARDRAILS |
| | RAMPS CONSTRUCTION/LOADING/GEOMETRY AND PROTECTION HAND |
| | RAILS/ GUARDRAILS |
| | (10) 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | VERTICAL ACCESSIBILITY STAIRS & RAMPS |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |