| 2016-09-15 16:24:27 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: TEMPORARY OFFICES AT MERRY PLACE |
| | JOB ADDRESS: 1914 MERRY PLACE |
| | DESCRIPTION: TEMPORARY STATE APPROVED MODULAR OFFICE |
| | SPACE. INCLUDING PLUMB, ELECTRIC, HVAC, FOUNDATION |
| | BLOCKING AND TIE-DOWN. |
| | MASTER PERMIT: 16090418 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. ELECTRICAL SUB PERMIT REQUIRED. |
| | 2. YOU SHALL SUBMIT A SITE PLANS INDICATING THE |
| | LOCATION OF THE ELECTRICAL POWER SOURCE WHETHER IT IS |
| | FROM A UTILITY POLE OR A TRANSFORMER. MARK ON THAT THE |
| | LOCATION OF THE TERMINAL RACK WITH THE METER AND |
| | SERVICE DISCONNECTS. MARK THE PROPOSED ROUTE FOR THE |
| | FEEDERS. |
| | 3. MARK ON THE PLAN THE PROPOSED ROUTE FROM THE |
| | TERMINAL RACK TO THE EXISTING SERVICE PANEL OF THE |
| | UNIT. |
| | 4. PROVIDE AN ELECTRICAL RISER DIAGRAM OF THE COMPLETE |
| | INSTALLATION FROM THE SOURCE TO THE INDIVIDUAL UNIT. |
| | INDICATE AS PART OF THE RISER THE RACEWAY AND CONDUCTOR |
| | TYPES. |
| | 5. FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER |
| | OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM |
| | OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR |
| | A MAXIMUM OF 3% VOLTAGE DROP. PROVIDE LOAD CALCS FOR |
| | THE SERVICE AND FEEDERS TAKING INTO ACCOUNT THE VARIOUS |
| | DISTANCES FOR VOLTAGE DROP CONSIDERATIONS. |
| | 6. NEC 110.27(B): IN LOCATIONS WHERE ELECTRICAL |
| | EQUIPMENT IS LIKELY TO BE EXPOSED TO PHYSICAL DAMAGE, |
| | ENCLOSURES OR GUARDS SHALL BE ARRANGED AND OF SUCH |
| | STRENGTH AS TO PREVENT SUCH DAMAGE. BOLLARDS MAY BE |
| | NECESSARY. |
| | 7. NEC 110.16: ELECTRICAL EQUIPMENT IN OTHER THAN |
| | DWELLING UNITS LIKELY TO REQUIRE SERVICE WHILE |
| | ENERGIZED SHALL BE FIELD MARKED TO WARN AGAINST |
| | POTENTIAL ARC-FAULT HAZARDS. |
| | 8. NEC 110.24: THE MAXIMUM AVAILABLE FAULT CURRENT |
| | SHALL BE DURABLY MARKED AND DATED ON ALL NON-DWELLING |
| | ELECTRICAL APPARATUS. |
| | 9. 1006.1 ILLUMINATION REQUIRED. THE MEANS OF EGRESS, |
| | INCLUDING THE EXIT DISCHARGE, SHALL BE ILLUMINATED AT |
| | ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF |
| | EGRESS IS OCCUPIED. |
| | 10. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION |
| | UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL |
| | INSPECTOR. NO SITE TUBES WILL BE ACCEPTED |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |