2016-10-12 15:16:381ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. KITCHEN SINK SHALL CONNECT TO BUILDING DRAIN
 DOWNSTREAM OF BATHROOM GROUP. PER FBC RES P3108.1
 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL SHALL BE PERMITTED TO
 BE VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL
 BE CONSIDERED THE VENT FOR THE FIXTURES AND SHALL
 EXTEND FROM THE CONNECTION OF THE DRY VENT ALONG THE
 DIRECTION OF THE FLOW IN THE DRAIN PIPE TO THE MOST
 DOWNSTREAM FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN
 SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH
 BEING WET VENTED OR SHALL HAVE A DRY VENT. EACH
 WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO
 THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR TANLESS WATER
 HEATER. PER WPB AMEND. TO FBC 107.2