| Plan Review Notes For Permit 16090395 |
| Permit Number |
16090395 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-12 15:16:38 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. KITCHEN SINK SHALL CONNECT TO BUILDING DRAIN | | | DOWNSTREAM OF BATHROOM GROUP. PER FBC RES P3108.1 | | | HORIZONTAL WET VENT PERMITTED. | | | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS | | | LOCATED ON THE SAME FLOOR LEVEL SHALL BE PERMITTED TO | | | BE VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL | | | BE CONSIDERED THE VENT FOR THE FIXTURES AND SHALL | | | EXTEND FROM THE CONNECTION OF THE DRY VENT ALONG THE | | | DIRECTION OF THE FLOW IN THE DRAIN PIPE TO THE MOST | | | DOWNSTREAM FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN | | | SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH | | | BEING WET VENTED OR SHALL HAVE A DRY VENT. EACH | | | WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO | | | THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL | | | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. | | | | | | 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR TANLESS WATER | | | HEATER. PER WPB AMEND. TO FBC 107.2 |
|