| 2016-09-14 14:50:47 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: |
| | JOB ADDRESS: 1018 14TH STREET |
| | DESCRIPTION: TRUSS REPAIR AND INTERIOR RENOVATION |
| | MASTER PERMIT: 16090395 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. YOU SHALL SUBMIT A SITE PLAN SHOWING THE LOCATION OF |
| | THE ELECTRIC UTILITY POLE SERVING THE RESIDENCE ALONG |
| | WITH THE LOCATION OF THE ELECTRIC METER AND MAIN |
| | DISCONNECT. YOU SHALL MARK BOTH, THE EXISTING AND |
| | PROPOSED LOCATIONS. YOU SHALL INDICATE IF THE SERVICE |
| | FEEDER IS AERIAL OR UNDERGROUND. |
| | 2. THE WORD ROMEX AS USED IN THIS NOTE IS TO IDENTIFY A |
| | TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE OF |
| | CABLE, REFER TO CABLE TYPES NM, NMC OR NMS. CORRECT |
| | ELECTRICAL SERVICE NOTES #10. |
| | 3. YOU SHALL COMPLETE THE A/C CHANGE-OUT FORM TO CROSS |
| | REFERENCE DETAILS FOR THE LOADS CALCS AND PANEL |
| | SCHEDULE. THIS WILL ALSO BE REQUIRED FOR THE MECHANICAL |
| | REVIEW. |
| | 4. NOTE THAT IT IS THE AMBIENT CONDITIONS WHICH |
| | DETERMINE CONDUCTOR INSULATION TYPE AND NOT THE WIRE |
| | GAUGE. ALL CONDUCTORS EXPOSED TO DAMP OR WET LOCATIONS |
| | SHALL BE LISTED ACCORDINGLY REGARDLESS OF GAUGE. |
| | CORRECT ELECTRICAL SPECIFICATIONS NOTE #3 ACCORDINGLY. |
| | 5. FBC-RE3602.2/NEC 220.82 SERVICE LOAD: CORRECT THE |
| | ELECTRICAL LOAD CALCS. YOUR FIGURES INDICATE 2660 SQ. |
| | FT. AND THE PROPERTY APPRAISER SHOWS ONLY 962 SQ. FT. |
| | FOR THE RESIDENCE. THE A/C CHANGE-OUT FORM INDICATES A |
| | 5KW HEATER; THE LOAD CALCS SHOW 10KW. CHECK THE MATH |
| | 6. THE FLOOR PLAN REFLECTS A RANGE W/AN OVEN AND ALSO A |
| | COOK TOP W/OVEN. THIS DIFFERS FROM THE CIRCUIT |
| | DIRECTORY AND LOAD CALCS. CORRECT ACCORDINGLY. |
| | 7. FBC-R4002.9 NEC 406.9(B) RECEPTACLES IN WET |
| | LOCATIONS. 15 AND 20 AMPERE, 125 AND 250 VOLT |
| | RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN |
| | ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE |
| | ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE, |
| | 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED |
| | WEATHER-RESISTANT TYPE WR. THIS CAN BE ADDRESSED WITH A |
| | BLOCK NOTE ADDED TO THE EXISTING NOTES. |
| | 8. FBC-RE3905.8 NEC 314.27(D) PADDLE FANS. BOXES USED |
| | FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY |
| | THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND |
| | INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED |
| | TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. THIS TOO |
| | CAN BE ADDRESSED WITH A BLOCK NOTE. |
| | 9. FBC-RE3903.3/NEC 210.70(A)(2)(B): AT LEAST ONE |
| | WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE |
| | INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR SIDE |
| | OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL ACCESS. |
| | THIS APPLIES TO THE DOOR LEADING OUTSIDE FROM THE |
| | LAUNDRY AREA. |
| | 10. FBC-RE3901.2.2 NEC 210.52 (A)(2) WALL SPACE. ANY |
| | WALL SPACE 2 FT. OR MORE IN WIDTH SHALL REQUIRE A |
| | RECEPTACLE. OUTLETS MISSING IN THE BEDROOMS ON THE WALL |
| | BETWEEN THE ENTRY DOOR AND THE CLOSET. |
| | 11. FBC-R404.1 LIGHTING EQUIPMENT (MANDATORY). A |
| | MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| | EFFICACY LAMPS. |
| | |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |