| Plan Review Notes For Permit 16090394 |
| Permit Number |
16090394 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-11-02 16:00:34 | REVISION 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] A GROUNDED CONDUCTOR SHALL NOT BE CONNECTED TO | | | NORMALLY NON-CURRENT-CARRYING METAL PARTS OF EQUIPMENT, | | | TO EQUIPMENT GROUNDING CONDUCTOR(S), OR BE RECONNECTED | | | TO GROUND ON THE LOAD SIDE OF THE SERVICE DISCONNECTING | | | MEANS. PLEASE SEPERATE NUETRAL FROM GROUND AT PANEL "C" | | | AS PER NEC 250.24(A)(5). |
|