| 2016-09-27 18:32:18 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: |
| | JOB ADDRESS: 4912 S. DIXIE HWY. |
| | DESCRIPTION: REVISION TO MASTER. |
| | MASTER PERMIT: 15090611 |
| | REVISION NUMBER: 16090394 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. SHEET E0.1: CORRECT NOTE PART I, C1 TO READY NEC |
| | 2011. |
| | 2. SHEET E2.1: FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: |
| | DAYLIGHT ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN |
| | THE DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF |
| | GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE |
| | WITH EITHER SECTION C405.2.2.3.1 OR SECTION |
| | C405.2.2.3.2. |
| | 3. SHEET E2.1: EXIT LIGHT MISSING AT THE WEST DOOR. |
| | 4. SHEET E2.2: FBC-R404.1 LIGHTING EQUIPMENT |
| | (MANDATORY). A MINIMUM OF 75 PERCENT OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICACY LAMPS. |
| | 5. SHEET E3.1: NEC 210.62 SHOW WINDOWS. AT LEAST ONE |
| | RECEPTACLE OUTLET SHALL BE INSTALLED WITHIN 18? OF THE |
| | TOP OF A SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR |
| | PORTION THEREOF AREA MEASURED HORIZONTALLY. |
| | 6. SHEET E3.2: IF ROOM 200 (KITCHEN) IS TO BE A KITCHEN |
| | AS PART OF THIS PERMIT, PROPER OUTLET PLACEMENT AND |
| | SPACING WILL BE REQUIRED ON DRAWINGS. IF IT IS NOT PART |
| | OF THIS SCOPE, A NOTE WILL BE ADDED TO EXCLUDE THE |
| | KITCHEN FROM THIS PERMIT. |
| | 7. SHEET E6.1: FBC-ER3609.3 NEC 250.94 BONDING FOR |
| | OTHER SYSTEMS. THE INTER-SYSTEM BONDING TERMINAL |
| | PRESCRIBED SHALL BE INSTALLED. |
| | 8. SHEET E6.1: FBC-RE3601.6.2 NEC 240.24 LOCATION IN OR |
| | ON PREMISES. (A) & (B) PANELS SHALL BE LOCATED SUCH |
| | THAT OVER CURRENT DEVICES ARE ACCESSIBLE AND THAT |
| | OCCUPANTS SHALL HAVE ACCESS TO OCP DEVICES. THIS |
| | APPLIES TO PANEL C WITH MDP NOT ACCESSIBLE. |
| | 9. SHEET E6.1: YOU SHALL INCLUDE WITH THE RISER DIAGRAM |
| | COMPLETE LOAD CALCS AS REQUIRED BY CODE. |
| | 10. FBC-R303.9 REQUIRED HEATING. WHEN THE WINTER DESIGN |
| | TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C), |
| | EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING |
| | FACILITIES CAPABLE OF MAINTAINING A MINIMUM ROOM |
| | TEMPERATURE OF 68?F (20?C) AT A POINT 3 FEET (914 MM) |
| | ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS |
| | IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE |
| | INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS |
| | SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS |
| | SECTION. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |