| Plan Review Notes For Permit 16090365 |
| Permit Number |
16090365 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-14 08:35:32 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- FLAT ROOF: CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY | | | FROM NOA 14-0529.02 SUBMITTED IS GOING TO BE INSTALLED | | | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301.1 FBC-RESIDENTIAL 5TH EDITION (2014). NOTE: SIGNED | | | AND SEALED RAS 117 CALCULATIONS MAY BE REQUIRED IF THE | | | DESIGN PRESSURES OF THE SELECTED ASSEMBLY DOESN'T MEET | | | THE DESIGN PRESSURES REQUIRED BY SEC. R301.1. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR THE ROOF TILE ADHESIVE TO BE | | | USED. SEE ROOF TILE NOA SUBMITTED FOR LISTED ADHESIVES. | | | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION SEEMS | | | TO BE LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS | | | AND CONTRACTORS OVERHEAD AND PROFIT AS REQUIRED BY SEC. | | | 109.3 CITY AMENDMENTS. SPECIFY TOTAL SQUARE FOOTAGE OF | | | FLAT AREA AND TOTAL SQUARE FOOTAGE OF ROOF TILE AREA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|