| Plan Review Notes For Permit 16090364 |
| Permit Number |
16090364 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-13 06:20:17 | 1) YOU HAVE SUBMITTED SPECIFICATIONS FOR FOUR DIFFERENT | | | MODELS OF A GREASE TRAP? WHICH MODEL IS BEING | | | INSTALLED? SUBMIT TWO COPIES OF SPECIFICATIONS ONLY FOR | | | THE MODEL BEING INSTALLED. WPB AMEND. TO FBC SEC. | | | 107.1. | | | 2) SUBMIT SIZING CALCULATIONS FOR THE GREASE TRAP. 2014 | | | FPV SEC. 1003.2. | | | 3) SUBMIT SANITARY RISER FOR PIPING TO BE INSTALLED. | | | SHOW ALL REQUIRED VENTS. | | | 4) ALL INDIRECT WASTE PIPING THAT EXCEEDS 30 INCHES IN | | | DEVELOPED LENGTH MEASURED HORIZONTALLY SHALL BE TRAPPED | | | OR 54 INCHES IN TOTAL DEVELOPED LENGTH SHALL BE | | | TRAPPED. | | | 5) WILL ANY OF THE PIPING BE INSTALLED UNDER THE SLAB/ | | | IF SO, SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 6) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE | | | GREASE TRAP.WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|