Plan Review Notes
Plan Review Notes For Permit 16090298
Permit Number 16090298
Review Stop P
Sequence Number 1
Notes
Date Text
2016-10-03 10:18:511ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW TOILET HEIGHT TO COMPLY WITH FBC ACC 604.4
 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 2. THE SIDE GRAB BAR SHALL COMPLY WITH FBC ACC FIGURE
 604.5.1 AND 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 3. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE,
 PER FBC ACC 609.4
  
 4. SHOW ACCESSIBILITY COMPLIANCE FOR WATER FOUNTAIN
 SHALL COMPLY WITH FBC ACC 306/307.2 /602.4/602.7