Plan Review Notes
Plan Review Notes For Permit 16090298
Permit Number 16090298
Review Stop E
Sequence Number 1
Notes
Date Text
2016-09-14 17:11:37JOB PERMIT NUMBER: 16090298
 JOB ADDRESS: 710 EXEC. CENTER DR
 WEST PALM BEACH FLORIDA
 DATE: SEPTEMBER 14, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014 (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1] LABEL SERVICE DISCONNECTS DENOTING EACH AREA SERVED
 AND IDENTIFY THE SOURCE OF POWER AT SUB-PANEL "LA" AS
 PER NEC 408.4(B) & NEC 225.37
  
 2] IN ACCORDANCE WITH SINGLE PHASE SHORT-CIRCUIT
 CALCULATIONS THE FAULT CURRENT IS 29,917.03 AMPS L+L AT
 THE SERVICE, HOWEVER FLOOR PLANS INDICATES PANELBOARD
 "LA" AT 22K AIC WHICH DOESN'T MATCH THE PANEL-SCHEDULE
 REFLECTING 10K AIC, PLEASE CLARIFY AND PROVIDE
 SHORT-CIRCUIT CALCULATIONS AT PANEL "LA" FOR
 VERIFICATION. NEC 110.9 & NEC 110.10
  
 3] THE GYM, SOCIAL ROOM, AND OFFICE AREA MUST COMPLY
 WITH MANDATORY LIGHTING CONTROLS SUCH AS DIMMERS,
 AUTOMATIC TIME SWITCHES, OCCUPANCY SENSORS AND ETC.
 FBC-E _ C405.2
  
 4] PROVIDE A LIGHT DENSITY CHART SHOWING THE INTERIOR
 POWER ALLOWANCES, TRADEOFFS PERMITTED USING THE SPACE
 BY SPACE METHOD. FBC-E _ C405.5
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. IF
 YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011