| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014 (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1] LABEL SERVICE DISCONNECTS DENOTING EACH AREA SERVED |
| | AND IDENTIFY THE SOURCE OF POWER AT SUB-PANEL "LA" AS |
| | PER NEC 408.4(B) & NEC 225.37 |
| | |
| | 2] IN ACCORDANCE WITH SINGLE PHASE SHORT-CIRCUIT |
| | CALCULATIONS THE FAULT CURRENT IS 29,917.03 AMPS L+L AT |
| | THE SERVICE, HOWEVER FLOOR PLANS INDICATES PANELBOARD |
| | "LA" AT 22K AIC WHICH DOESN'T MATCH THE PANEL-SCHEDULE |
| | REFLECTING 10K AIC, PLEASE CLARIFY AND PROVIDE |
| | SHORT-CIRCUIT CALCULATIONS AT PANEL "LA" FOR |
| | VERIFICATION. NEC 110.9 & NEC 110.10 |
| | |
| | 3] THE GYM, SOCIAL ROOM, AND OFFICE AREA MUST COMPLY |
| | WITH MANDATORY LIGHTING CONTROLS SUCH AS DIMMERS, |
| | AUTOMATIC TIME SWITCHES, OCCUPANCY SENSORS AND ETC. |
| | FBC-E _ C405.2 |
| | |
| | 4] PROVIDE A LIGHT DENSITY CHART SHOWING THE INTERIOR |
| | POWER ALLOWANCES, TRADEOFFS PERMITTED USING THE SPACE |
| | BY SPACE METHOD. FBC-E _ C405.5 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES.WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. |