2016-09-14 12:56:031ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: WILLIAMS ADDITION
 JOB ADDRESS: 1353 13TH ST.
 DESCRIPTION: ADDITION TO HOUSE
 MASTER PERMIT: 16090274
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. YOU SHALL MARK ON THE SITE PLAN THE LOCATION OF THE
 ELECTRIC UTILITY POLE SERVING THE RESIDENCE ALONG WITH
 THE LOCATION OF THE ELECTRIC METER AND MAIN DISCONNECT.
 YOU SHALL INDICATE IF THE SERVICE FEEDER IS AERIAL OR
 UNDERGROUND.
 2. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 3. THE WORD ?OUTLET? AS EXPRESSED IN NEC 210.12(B) DOES
 NOT IMPLY RECEPTACLES ONLY; IT REFERS TO EVERY OUTLET
 (MEANING EVERY CIRCUIT IN THE NAMED AREAS). CORRECT
 NOTE 5 ACCORDINGLY.
 4. FBC-RE4003.5 RECESSED INCANDESCENT LUMINAIRES:
 RECESSED INCANDESCENT LUMINAIRES SHALL HAVE THERMAL
 PROTECTION AND SHALL BE LISTED AS THERMALLY PROTECTED.
 5. FBC-RE3905.8 NEC 314.27(D) PADDLE FANS. BOXES USED
 FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY
 THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND
 INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED
 TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS.
 6. FBC-RE3602.2/NEC 220.82 SERVICE LOAD: THE MINIMUM
 LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND SERVICE
 DEVICES THAT SERVE 100 PERCENT OF THE DWELLING UNIT
 LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE
 E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE
 DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE
 DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR
 FEEDERS IN ACCORDANCE WITH CHAPTER 37. PROVIDE A SITE
 SPECIFIC AND LEGIBLE LOAD CALC. SUBMIT A SITE SPECIFIC
 RISER DIAGRAM, INCLUDE CONDUCTOR TYPES AND SIZING.
 7. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A
 PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING
 THE SPECIFIC PURPOSE OF EVERY CIRCUIT. PROVIDE A SITE
 SPECIFIC CIRCUIT DIRECTORY FOR EVERY PANEL
 8. SHOW ON THE ELECTRICAL PLAN THE LOCATION OF ALL HVAC
 EQUIPMENT AND THE REQUIRED SERVICE OUTLET.
 9. FBC-ER404.1: A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  