| 2016-09-14 12:56:03 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: WILLIAMS ADDITION |
| | JOB ADDRESS: 1353 13TH ST. |
| | DESCRIPTION: ADDITION TO HOUSE |
| | MASTER PERMIT: 16090274 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. YOU SHALL MARK ON THE SITE PLAN THE LOCATION OF THE |
| | ELECTRIC UTILITY POLE SERVING THE RESIDENCE ALONG WITH |
| | THE LOCATION OF THE ELECTRIC METER AND MAIN DISCONNECT. |
| | YOU SHALL INDICATE IF THE SERVICE FEEDER IS AERIAL OR |
| | UNDERGROUND. |
| | 2. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY |
| | A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE |
| | OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?. |
| | 3. THE WORD ?OUTLET? AS EXPRESSED IN NEC 210.12(B) DOES |
| | NOT IMPLY RECEPTACLES ONLY; IT REFERS TO EVERY OUTLET |
| | (MEANING EVERY CIRCUIT IN THE NAMED AREAS). CORRECT |
| | NOTE 5 ACCORDINGLY. |
| | 4. FBC-RE4003.5 RECESSED INCANDESCENT LUMINAIRES: |
| | RECESSED INCANDESCENT LUMINAIRES SHALL HAVE THERMAL |
| | PROTECTION AND SHALL BE LISTED AS THERMALLY PROTECTED. |
| | 5. FBC-RE3905.8 NEC 314.27(D) PADDLE FANS. BOXES USED |
| | FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY |
| | THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND |
| | INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED |
| | TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. |
| | 6. FBC-RE3602.2/NEC 220.82 SERVICE LOAD: THE MINIMUM |
| | LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND SERVICE |
| | DEVICES THAT SERVE 100 PERCENT OF THE DWELLING UNIT |
| | LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE |
| | E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE |
| | DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE |
| | DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR |
| | FEEDERS IN ACCORDANCE WITH CHAPTER 37. PROVIDE A SITE |
| | SPECIFIC AND LEGIBLE LOAD CALC. SUBMIT A SITE SPECIFIC |
| | RISER DIAGRAM, INCLUDE CONDUCTOR TYPES AND SIZING. |
| | 7. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A |
| | PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING |
| | THE SPECIFIC PURPOSE OF EVERY CIRCUIT. PROVIDE A SITE |
| | SPECIFIC CIRCUIT DIRECTORY FOR EVERY PANEL |
| | 8. SHOW ON THE ELECTRICAL PLAN THE LOCATION OF ALL HVAC |
| | EQUIPMENT AND THE REQUIRED SERVICE OUTLET. |
| | 9. FBC-ER404.1: A MINIMUM OF 75% OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICIENCY LAMPS. |
| | |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |