2016-10-21 18:10:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A-1.0 THE COMPONENT AND CLADDING PRESSURES
 FOR ROOF ZONES 1, 2 & 3 ARE INCORRECT FOR A ONE STORY
 STRUCTURE WITH A 3/12 ROOF SLOPE IN EXPOSURE CATEGORY C
 WITH A 170 MPH VULT WINDSPEED. THE WINDSPEEDS THAT WERE
 CALCULATED BASED ON FBCR TABLE R301.2(2) AND R301.2(3)
 ARE +21.9, -35.4 PSF FOR ZONE 1, +21.9, -60.4 PSF FOR
 ZONE 2 AND +21.9, -89.4 PSF FOR ZONE 3. PLEASE RECHECK
 THE PRESSURES THAT WERE SPECIFIED ON THE PLANS AND MAKE
 CORRECTIONS AS NECESSARY.
  
 2) FBC R403.1.4 REQUIRES THE BOTTOM OF EXTERIOR
 FOOTINGS TO BE AT LEAST 12 INCHES BELOW GRADE. PLEASE
 REVISE THE WALL SECTION ON SHEET A1.1 ACCORDINGLY.
  
 3) SPECIFY THE SIZES OF THE DOORS ON THE PLANS. FBC
 107.2.1
  
 4) SHOW COMPLIANCE WITH FBC R 807.1 FOR ATTIC ACCESS TO
 THE ADDITION.
  
 5) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORM R405. FBC ENERGY SECTION R103.1.1.2
  
 6) THE TRUSS ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 IS REQUIRED ON THE ROOF TRUSS DRAWINGS AND THE ROOF
 TRUSS LAYOUTS. SIGNATURE STAMPS, COPIES OR OTHER
 FACSIMILES ARE NOT ACCEPTABLE PER FAC 61G15-23.002.