| Plan Review Notes For Permit 16090274 |
| Permit Number |
16090274 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-21 18:10:01 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ON SHEET A-1.0 THE COMPONENT AND CLADDING PRESSURES | | | FOR ROOF ZONES 1, 2 & 3 ARE INCORRECT FOR A ONE STORY | | | STRUCTURE WITH A 3/12 ROOF SLOPE IN EXPOSURE CATEGORY C | | | WITH A 170 MPH VULT WINDSPEED. THE WINDSPEEDS THAT WERE | | | CALCULATED BASED ON FBCR TABLE R301.2(2) AND R301.2(3) | | | ARE +21.9, -35.4 PSF FOR ZONE 1, +21.9, -60.4 PSF FOR | | | ZONE 2 AND +21.9, -89.4 PSF FOR ZONE 3. PLEASE RECHECK | | | THE PRESSURES THAT WERE SPECIFIED ON THE PLANS AND MAKE | | | CORRECTIONS AS NECESSARY. | | | | | | 2) FBC R403.1.4 REQUIRES THE BOTTOM OF EXTERIOR | | | FOOTINGS TO BE AT LEAST 12 INCHES BELOW GRADE. PLEASE | | | REVISE THE WALL SECTION ON SHEET A1.1 ACCORDINGLY. | | | | | | 3) SPECIFY THE SIZES OF THE DOORS ON THE PLANS. FBC | | | 107.2.1 | | | | | | 4) SHOW COMPLIANCE WITH FBC R 807.1 FOR ATTIC ACCESS TO | | | THE ADDITION. | | | | | | 5) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE | | | ENERGY FORM R405. FBC ENERGY SECTION R103.1.1.2 | | | | | | 6) THE TRUSS ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE | | | IS REQUIRED ON THE ROOF TRUSS DRAWINGS AND THE ROOF | | | TRUSS LAYOUTS. SIGNATURE STAMPS, COPIES OR OTHER | | | FACSIMILES ARE NOT ACCEPTABLE PER FAC 61G15-23.002. |
|