| Notes |
| Date |
Text |
| 2016-11-22 07:35:51 | 1) WHAT ARE THE DIMENSIONS OF THE LOUVERS IN THE | | | GARAGE? YOU HAVE SUPPLIED THE TOTAL SQUARE INCH AREA | | | BUT NOT THE LENGTH & WIDTH. ISN'T THE TANKLESS WATER | | | HEATER A DIRECT VENT APPLIANCE? IF SO, WHY ARE | | | COMBUSTION AIR OPENINGS BEING PROVIDED? CLARIFY. | | | 2) THE LOUVER OPENINGS FOR THE DRYER ARE | | | UNDERSIZED.COMPLY WITH SEC. 2014 FBCR SEC.G2407.5.3.1, | | | EACH OPENING SHALL HAVE A MINIMUM OF 100 SQUARE INCHES | | | OF FREE AREA. METAL LOUVERS AND GRILLS SHALL BE ASSUMED | | | TO HAVE A 75 PERCENT FREE AREA. 2014 FBBCR | | | SEC.G2407.10. THEREFORE, THE TOTAL SQUARE INCH AREA OF | | | THE LOUVERS SHALL BE MULTIPLIED BY 75 PERCENT TO OBTAIN | | | THE FREE AREA.THE SIZE GRILL YOU HAVE SPECIFIED WILL | | | NOT WORK. | | | 3) THE RINNAI SPECIFICATION SHEET STATES THAT THE | | | MAXIMUM BTU LOAD IS 180,000 BUT THE GAS PLAN SHOWS | | | 225,00 BTU'S. CLARIFY. | | | 4) THE COPY OF THE CODE THAT WAS SUBMITTED FOR THE | | | COMBUSTION AIR OPENINGS IS FROM THE 2007 FBC | | | MECHANICAL. THE CODE IN EFFECT IS THE 2014 FBC NOT THE | | | 2007. I REFERENCED THE APPLICABLE CODE AND SECTION FOR | | | COMBUSTION AIR IN MY PREVIOUS GAS REVIEW. I SUGGEST | | | REFERRING TO IT. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|