Plan Review Notes
Plan Review Notes For Permit 16090271
Permit Number 16090271
Review Stop G
Sequence Number 4
Notes
Date Text
2016-11-22 07:35:511) WHAT ARE THE DIMENSIONS OF THE LOUVERS IN THE
 GARAGE? YOU HAVE SUPPLIED THE TOTAL SQUARE INCH AREA
 BUT NOT THE LENGTH & WIDTH. ISN'T THE TANKLESS WATER
 HEATER A DIRECT VENT APPLIANCE? IF SO, WHY ARE
 COMBUSTION AIR OPENINGS BEING PROVIDED? CLARIFY.
 2) THE LOUVER OPENINGS FOR THE DRYER ARE
 UNDERSIZED.COMPLY WITH SEC. 2014 FBCR SEC.G2407.5.3.1,
 EACH OPENING SHALL HAVE A MINIMUM OF 100 SQUARE INCHES
 OF FREE AREA. METAL LOUVERS AND GRILLS SHALL BE ASSUMED
 TO HAVE A 75 PERCENT FREE AREA. 2014 FBBCR
 SEC.G2407.10. THEREFORE, THE TOTAL SQUARE INCH AREA OF
 THE LOUVERS SHALL BE MULTIPLIED BY 75 PERCENT TO OBTAIN
 THE FREE AREA.THE SIZE GRILL YOU HAVE SPECIFIED WILL
 NOT WORK.
 3) THE RINNAI SPECIFICATION SHEET STATES THAT THE
 MAXIMUM BTU LOAD IS 180,000 BUT THE GAS PLAN SHOWS
 225,00 BTU'S. CLARIFY.
 4) THE COPY OF THE CODE THAT WAS SUBMITTED FOR THE
 COMBUSTION AIR OPENINGS IS FROM THE 2007 FBC
 MECHANICAL. THE CODE IN EFFECT IS THE 2014 FBC NOT THE
 2007. I REFERENCED THE APPLICABLE CODE AND SECTION FOR
 COMBUSTION AIR IN MY PREVIOUS GAS REVIEW. I SUGGEST
 REFERRING TO IT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW