| Plan Review Notes For Permit 16090271 |
| Permit Number |
16090271 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-11-07 14:00:35 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED | | | IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR | | | OTHER APPROVED HEATING AND COOLING CALCULATION | | | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE | | | DIRECTIONAL ORIENTATION OF THE BUILDING. THE | | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH | | | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN | | | CONDITIONS DESCRIBED IN | | | SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER | | | SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR | | | OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM | | | SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY | | | LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS | | | STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS. | | | | | | (1) PROVIDE EQUIPMENT SCHEDULE AS PER R403.6.1 FBC | | | MECHANICAL 2014. (SEE ABOVE) | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | | | | | | | | | | | | | | | | |
|