| 2016-10-25 09:58:04 | 1) THE ENERGY CALCULATIONS NOTE THE GAS FOR THE WATER |
| | HEATER AS PROPANE AND THE GAS DRAWING NOTES NATURAL |
| | GAS. CLARIFY. |
| | 2) THE SUBMITTED GAS SIZING TABLES ARE FROM AN OUTDATED |
| | CODE. SUBMIT COPIES OF THE APPROPRIATE SIZING TABLES |
| | FROM THE 2014 FBC-FUEL GAS CODE. |
| | 3) THE BTU LOAD OF THE FUTURE BBQ AND THE POOL HEATER |
| | SHALL BE INCLUDED IN THE TOTAL BTU FOR THE SIZING LOAD |
| | OF THE SYSTEM. THE PLANS SHOW A GAS DRYER ON THE 2ND |
| | FLOOR. THIS SHALL ALSO BE ADDED INTO THE TOTAL BTU |
| | LOAD. SIZE THE SYSTEM FOR THE TOAL BTU LOAD. |
| | 4) THE GAS DRYER SHALL BE INCLUDED ON THE GAS RISER |
| | DIAGRAM. WPB AMEND. TO FBC SEC. 107.3.5.3. |
| | 5) SUBMIT A COMPLETE GAS RISER DIAGRAM SHOWING ALL THE |
| | TYPES OF PIPE BEING INSTALLED AND THAT CLEARLY SHOWS |
| | THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 |
| | FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES |
| | SEC. G2413. |
| | 6) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014 |
| | FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G |
| | 2413.3. THE GAS DRYER ON THE 2ND FLOOR MAY CHANGE THIS |
| | DISTANCE. |
| | 7) SHOW THE LOCATION OF THE GAS METER, AND THE |
| | APPROXIMATE LOCATION OF THE FUTURE POOL HEATER AND BBQ |
| | ON THE FLOOR PLAN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 8) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | COOKTOP AND THE DRYER PER THE 2014 FBC-FUEL GAS CODE |
| | SEC.304.1 OR 2014 FBC-RES. SEC. G 2407. |
| | 9) SHOW ALL PIPE SIZES, AND THE CORRESPONDING EHD |
| | NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |