| Plan Review Notes For Permit 16090271 |
| Permit Number |
16090271 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-24 13:35:53 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO'S (RED-LINED ON | | | PLANS) | | | | | | 1] PERMANENT LIGHTING SHALL BE 75% HIGH EFFICIENCY AND | | | RECESSED FIXTURES SHALL BE LISTED IC-RATED SEALED TO | | | NOT COMPROMISE BUILDING THERMAL ENVELOPE. FBC-E | | | SECTIONS R402.4.4 & R404.1 ADD TO ELECTRICAL NOTES. | | | | | | 2] ALL 1ST FLOOR SWITCHES CONTROLLING LIGHTING LOADS | | | SHALL HAVE A GROUNDED (NEUTRAL) CONDUCTOR AT THE SWITCH | | | LOCATION. FUTURE INSTALLATION WOULDN'T BE ACCESSIBLE | | | WITH THE ADDITION OF THE 2ND FLOOR. FBC-R SECTION | | | E4001.15 | | | |
|