| 2016-10-11 18:47:33 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | (1) PROVIDE EQUIPMENT SCHEDULE AS PER R403.6.1 FBC | | | MECHANICAL 2014 | | | (2) PROVIDE CFM VALUES FOR AL SUPPLY OUTLETS. | | | (3) PROVIDE RETURN AIR FROM ALL BEDROOMS. (2ND FLOOR | | | PROPOSED BEDROOM IS MISSING RETURN). | | | (4) PROVIDE EXHAUST DUCT DETAIL IN ALL BATHROOMS. SHOW | | | ALL DUCT SIZES AND EXHAUST AMOUNTS. | | | (5) PROVIDE CONDENSER TIE DOWN DETAIL AS PER 2014 FBC | | | WIND LOAD REQUIREMENTS. | | | (6) PROVIDE CLARIFICATION FOR KITCHEN EXHAUST. | | | RECIRCULATING OR VENTED?? IF VENTED PROVIDE DETAIL WITH | | | DUCT SIZE AND EXHAUST AMOUNT. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | (7) FORM R405-2014 MUST BE SIGNED BY "OWNER/AGENT" | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | |
|