| Date |
Text |
| 2016-09-12 16:23:46 | JOB PERMIT NUMBER: 16090271 |
| | JOB ADDRESS: 224 BELMONTE ROAD |
| | WEST PALM BEACH FLORIDA 33405 |
| | DATE: SEPTEMBER 12, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1] PROVIDE EXISTING ELECTRIC SERVICE RISER WITH WIRE |
| | SIZES AND SPECIFY IF ADEQUATE TO HANDLE ADDED LOADS, |
| | CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE NEW |
| | REVISED LOAD CALCULATIONS, PANEL SCHEDULES AND IDENTIFY |
| | NEW CIRCUITS ON FLOOR PLAN. FBC- 107.3.5.3 |
| | |
| | 2] PERMANENT LIGHTING SHALL BE 75% HIGH EFFICIENCY AND |
| | RECESSED FIXTURES SHALL BE LISTED IC-RATED SEALED TO |
| | NOT COMPROMISE BUILDING THERMAL ENVELOPE. FBC-E |
| | SECTIONS R402.4.4 & R404.1 ADD TO ELECTRICAL NOTES. |
| | |
| | 3] ALL 1ST FLOOR SWITCHES CONTROLLING LIGHTING LOADS |
| | SHALL HAVE A GROUNDED (NEUTRAL) CONDUCTOR AT THE SWITCH |
| | LOCATION. FUTURE INSTALLATION WOULDN'T BE ACCESSIBLE |
| | WITH THE ADDITION OF THE 2ND FLOOR. FBC-R SECTION |
| | E4001.15 |
| | |
| | 4] KITCHEN-ISLAND SHALL HAVE A GFCI RECEPTACLE OUTLET |
| | AT BOTH ENDS WITHIN 12'' OF THE COUNTERTOP. FBC-R |
| | SECTION E3901.4.2 |
| | |
| | 5] ACCU # 1, ACCU # 2, AND POOL PUMP REFLECT |
| | DISCONNECTS BEHIND THE EQUIPMENT PLEASE RELOCATE TO |
| | COMPLY WITH WORKING CLEARANCES. FBC-R SECTION E3405.1 |
| | |
| | 6] MISSING CARBON MONOXIDE ALARM BY THE UP-STAIRS |
| | LANDING AND A SMOKE ALARM IN THE MASTER BEDROOM PER |
| | FBC-R 314 & 315. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES.WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. IF |
| | YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |