| 2016-09-16 10:00:47 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA RES BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND |
| | LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC |
| | RATINGS. FBC 107.3.5 |
| | 2. REVISE SERVICE CONDUCTORS, UNDERSIZED FOR A 400AMP |
| | SERVICE. FBC RES E3603 |
| | 3. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS |
| | FOR LOW VOLTAGE SYSTEMS AND POOL. FBC 107.3.5 |
| | 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE |
| | PER FBC RES E3609.3 |
| | 5. GROUNDING ELECTRODE CONDUCTOR IS UNDERSIZED FOR |
| | 400AMP SERVICE. #2 REQUIRED PER NEC 250.66. FBC RES |
| | E3603 |
| | 6. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT |
| | GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC |
| | 107.3.5 |
| | 7. PLEASE NOTE THAT THE RISER DIAGRAM DOES NOT MATCH |
| | THE FLOOR PLAN LAYOUT OF PANEL LOCATION. IF 400A PANEL |
| | IS LOCATED IN GARAGE SHOWN AS A 200AMP PANEL, CORRELATE |
| | AND CORRECT. IF THERE IS A MAIN CB, AS SHOWN OUTSIDE |
| | PLEASE SHOW ON RISER DIAGRAM. LABEL EQUIPMENT AS RATED |
| | FOR SERVICE ENTRANCE AND PROPER NEMA 3R RATING. FBC |
| | 107.3.5 |
| | 8. CLARIFY BUS RATING FOR PANEL P SHOWN AT 60AMP; IS IT |
| | 100 AMP POOL PANEL? TYPICAL. FBC 107.3.5 |
| | 9. AT THE RISER DIAGRAM SHOW CONDUCTOR SIZE FOR PANEL |
| | B. FBC RES E3603 |
| | 10. SHOW EXTERIOR RECEPTACLE AT REAR PROTECTED BY GFCI |
| | DEVICE. FBC RES E3902.3 |
| | 11. RECEPTACLE AT WALL SPACE IN KITCHEN AREA WITHIN 6FT |
| | OF SINK TO BE LABELED AS GFCI PROTECTED. FBC RES |
| | E3902.7 |
| | 12. RECEPTACLE AT WALL SPACE IN WET BAR AREA WITHIN 6FT |
| | OF SINK TO BE LABELED AS GFCI PROTECTED. FBC RES |
| | E3902.7 |
| | 13. SHOW JACUZZI AND GARAGE DOOR OPENER DEVICES TO BE |
| | PROTECTED BY GFCI BREAKER TO BE READILY ACCESSIBLE. A |
| | NOTE WILL SUFFICE. |
| | 14. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE |
| | PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE |
| | HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET |
| | THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2 |
| | ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5 |
| | 15. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER |
| | RESISTANT RECEPTACLE THROUGHOUT. FBC RES E4002.14 |
| | 16. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO |
| | INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS. |
| | 17. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR |
| | DINING ROOM RECEPTACLES AND BATHROOM RECEPTACLES. FBC |
| | RES E3703.2 AND 4 |
| | 18. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| | QUESTIONS OR CONCERNS. |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |