| 2016-09-13 10:39:15 | RESIDENTIAL (R3) REVISION/SUBMITTAL BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- ROOF TILES FLORIDA PRODUCT APPROVAL FL3505-R7 |
| | SUBMITTED: ENGINEER OF RECORD TO CLEARLY SPECIFY ROOF |
| | TILE FASTENING METHOD AS REQUIRED BY SEC. 107.2.1.2 |
| | CITY AMENDMENTS. IF SPECIFYING SCREWS, THEN SPECIFY |
| | SIZE AND NUMBER OF SCREWS. IF SPECIFYING ADHESIVE, THEN |
| | PROVIDE 2 COPIES OF THE ADHESIVE PRODUCT APPROVAL |
| | LISTED ON THE ROOF TILE PRODUCT APPROVAL. REPEAT |
| | COMMENT. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) INSWING FRENCH DOORS AS SHOWN ON PLANS. |
| | FLORIDA PRODUCT APPROVAL FL253-R16 WITH CORRESPONDING |
| | NOA 16-0126.04 SUBMITTED IS FOR OUTSWING DOORS. CLARIFY |
| | WHY SUBMITTING 4 COPIES OF THE SAME PRODUCT APPROVAL. |
| | ONLY 2 ARE REQUIRED. NEED INSWING DOORS AS SHOWN ON |
| | PLANS. REPEAT COMMENT. |
| | |
| | B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK |
| | MULLION SIZE TO BE USED TO VERIFY COMPLIANCE WITH |
| | CALCULATED DESIGN PRESSURES. REPEAT COMMENT. |
| | |
| | C) ALL PRECAST LINTELS AS SPECIFIED ON PLANS. REPEAT |
| | COMMENT. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW/APPROVE IN WRITING ALL |
| | PRODUCT APPROVALS, INCLUDING THE ROOF TILES AS REQUIRED |
| | BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 4- CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR SLIDING |
| | GLASS DOORS (FL12796-R7). APPROVED PLANS DON'T INCLUDE |
| | THIS TYPE OF DOOR. SEC. 107.2.1 CITY AMENDMENTS. ALSO, |
| | FLORIDA PRODUCT APPROVAL SUBMITTED DOESN'T MEET THE |
| | CALCULATED DESIGN PRESSURES SHOWN ON SHEET S2. |
| | |
| | 5- CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR CASEMENT |
| | WINDOWS ( FL13999-R6). APPROVED PLANS DON'T INCLUDE |
| | THIS WINDOW. SEC. 107.2.1 CITY AMENDMENTS. ALSO, |
| | FLORIDA PRODUCT APPROVAL SUBMITTED DOESN'T MEET THE |
| | CALCULATED DESIGN PRESSURES SHOWN ON SHEET S2. |
| | |