2016-10-31 14:02:402ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090886
 10/31/2016
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS: THE NEW
 SOIL HOLDING ROOM 008 MUST BE UNDER NEGATIVE PRESSURE
 WITH ALL AIR EXHAUSTED TO THE OUTDOORS PER TABLE 7-1
 ASHRAE 170-2008. PLEASE REVISE THE PLANS TO SHOW THE
 REQUIORED SYSTEM, AND PROVIDE THE ACH RATES FOR THE
 ROOM AND ALL OTHER NEW ROOMS CONSTRUCTED UNDER THIS
 PERMIT INCLUDING THE CENTRAL SUPPLY-009, THE MEDICAL
 SUPPLY-011, AND THE NURSE'S STATION-012.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER