| Plan Review Notes For Permit 16090195 |
| Permit Number |
16090195 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-31 14:02:40 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16090886 | | | 10/31/2016 | | | | | | 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS: THE NEW | | | SOIL HOLDING ROOM 008 MUST BE UNDER NEGATIVE PRESSURE | | | WITH ALL AIR EXHAUSTED TO THE OUTDOORS PER TABLE 7-1 | | | ASHRAE 170-2008. PLEASE REVISE THE PLANS TO SHOW THE | | | REQUIORED SYSTEM, AND PROVIDE THE ACH RATES FOR THE | | | ROOM AND ALL OTHER NEW ROOMS CONSTRUCTED UNDER THIS | | | PERMIT INCLUDING THE CENTRAL SUPPLY-009, THE MEDICAL | | | SUPPLY-011, AND THE NURSE'S STATION-012. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|