| 2016-10-31 07:32:47 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16090195 |
| | ADD: 5300 EAST AVE. |
| | CONT: TRILLIUM CONSTRUCTION |
| | TEL: 561-296-0700 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. OCT. 31/2016 |
| | ACTION: DENIED |
| | |
| | 1-4) COMPLIED. |
| | |
| | 5) 2ND REQUEST. SEMI-COMPLIED. SHEET A-8 DOES PROVIDE |
| | THE VASD PRESSURES FOR THE NEW DOOR OPENINGS. |
| | WHAT IS STILL MISSING IS THE ACTUAL WIND DESIGN |
| | CRITERIA. IT LOOKS LIKE THE PRESSURES ARE FOR AN B |
| | EXPOSURE FOR 50 SQUARE FEET OPENING OF BY +6.3.PSF AND |
| | -3.24 PSF. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| | INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| | REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| | THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| | |
| | 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 5.2. RISK CATEGORY. |
| | |
| | 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 1ST ROUND OF COMMENTS. SHEET A1 ROOMS 111-115 SHOW THE |
| | INSTALLATION OF NEW EXTERIOR DOORS, SHEET SHOWS DETAILS |
| | FOR THE NEW STOREFRONT SYSTEM BUT I COULD NOT FIND |
| | WHERE THE 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 6) SEMI-COMPLIED. THIS REVIEW (1) PRODUCT APPROVAL FOR |
| | EXTERIOR DOORS WAS SUBMITTED TRULITE (NOA 14-0225.02) |
| | AND (1) TRULITE STOREFRONT WINDOW WALL SYSTEM |
| | NOA(14-0203.01. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.1 REQUIRES A MINIMUM OF 2 PRODUCT |
| | APPROVALS TO BE SUBMITTED. |
| | |
| | 1ST ROUND OF COMMENTS. PLEASE NOTE A SERIES 35H YKK AP |
| | AMERICA OUTSWING ENTRANCE DOORS TECHNICAL SHEETS WERE |
| | SUBMITTED, THEY DO NOT HAVE ANY INDICATION IF THEY ARE |
| | A FLORIDA APPROVAL OR A MIAMI-DADE NOA. 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7A) NEW COMMENT. TRULITE NOA 14-0225.02 SEE PAGE 4 OF |
| | 11 OVER HANG REQUIREMENTS FOR WATER INFILTRATION ARE |
| | NOT MET SEE 1710.5.1 EXCEP. # 2 . |
| | |
| | 7B) NEW COMMENT. TRULITE NOA 14-0225.02 SEE PAGE 4 OF |
| | 11, FOR AN ACCESSIBLE THRESHOLD(ADA-ACCESSIBLE) THE |
| | THRESHOLD TO BE INSTALLED AND COMPLIANCE WITH WATER |
| | INFILTRATION THE 1/2 INCH THRESHOLD IS LIMITED TO LESS |
| | OR EQUAL TO +33.3 PSF PRESSURE. |
| | |
| | 8)COMPLIED. MICROWAVE. |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |