| Plan Review Notes For Permit 16090195 |
| Permit Number |
16090195 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-19 05:14:35 | 1) SHT. A-6 - SHOW THE LENGTH AND WIDTH DIMENSIONS OF | | | THE NEW TOILET ROOM. A MINIMUM WIDTH OF 85 INCHES IS | | | REQUIRED IF BUILT PERFECT. 86 INCHES ALLOWS FOR | | | TOLERANCE. | | | 2) SHT. P-1 SHOWS AIR CHAMBERS ON THE WATER PIPING. AIR | | | CHAMBERS ARE NOT PERMITTED.A WATER HAMMER ARRESTOR | | | SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE | | | UTILIZED. WATER HAMMER ARRESTORS SHALL CONFORM TO ASSE | | | 1010. FPC SEC.604.9. | | | 3) SHT. PD-1 - PLANS SHOW THE REMOVAL OF THE DRINKING | | | FOUNTAINS IN FAMILY SUPPORT ROOMS # 216 & 316. THIS | | | APPEARS TO CREATE A PLUMBING CODE VIOLATION AS DRINKING | | | FOUNTAINS ARE REQUIRED. WHERE WILL THESE FOUNTAINS BE | | | RELOCATED OR ADDED? CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|