Plan Review Notes
Plan Review Notes For Permit 16090195
Permit Number 16090195
Review Stop M
Sequence Number 1
Notes
Date Text
2016-09-12 16:20:231ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16090195
 9/12/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS AND RATES
 FOR ALL ROOMS AND SPACES UNDERGOING RENOVATIONS-
 SEETABLE 403.3 FBC-14 MECHANICAL, TABLE 6-4 ASHRAE
 62.1-2010, AND TABLE 7-1 ASHRAE STANDARD 170- 2008.
 PLEASE NOTE THAT PER THE ASHRAE STANDARSDS, NEGATIVE
 PRESSURE (EXHAUST) IS REQUIRED FOR THE
 SOILED HOLDING ROOMS AND SOILED WORKROOMS.
  
 2) SHOW THE LOCATIONS OF RETURN GRILLS IN THE FAMILY
 SUPPORT ROOMS, AND NURSE STATIONS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  