| 2016-09-12 16:20:23 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16090195 | | | 9/12/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS AND RATES | | | FOR ALL ROOMS AND SPACES UNDERGOING RENOVATIONS- | | | SEETABLE 403.3 FBC-14 MECHANICAL, TABLE 6-4 ASHRAE | | | 62.1-2010, AND TABLE 7-1 ASHRAE STANDARD 170- 2008. | | | PLEASE NOTE THAT PER THE ASHRAE STANDARSDS, NEGATIVE | | | PRESSURE (EXHAUST) IS REQUIRED FOR THE | | | SOILED HOLDING ROOMS AND SOILED WORKROOMS. | | | | | | 2) SHOW THE LOCATIONS OF RETURN GRILLS IN THE FAMILY | | | SUPPORT ROOMS, AND NURSE STATIONS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|