Plan Review Notes
Plan Review Notes For Permit 16090195
Permit Number 16090195
Review Stop E
Sequence Number 1
Notes
Date Text
2016-09-15 12:07:46ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: PATIENT WING IMPROVEMENTS
 JOB ADDRESS: 5300 EAST AVE.
 DESCRIPTION: INTERIOR IMPROVEMENTS TO PATIENT ROOMS &
 UPGRADES TO VARIOUS CORRIDORS & OTHER AREAS
 MASTER PERMIT: 16090195
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 SHEET E2
 1. PANTRY 027- NEC 210.8: GFI PROTECTION REQUIRED FOR
 OUTLETS ON KITCHEN COUNTER.
 2. EXISTING RESIDENT ROOMS, EXISTING PANTRIES 217 &
 317, AND MED 011- NEC 210.8: GFI PROTECTION REQUIRED
 FOR OUTLETS WITHIN 6 FT. OF SINK.
 3. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
 SHEET E3
 1. EXIST COUNSEL 309, EXIST CORR. 024-THERE APPEARS TO
 BE A MISPLACED OR INCORRECTLY LABELED EXIT LIGHT
 2. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 THERE DOES NOT APPEAR TO BE DAYLIGHT ZONIFICATION.
 SHEET E5
 1. PANEL LD CIRCUIT 35 FOR THE EWC SHALL BE GFI
 PROTECTED AT EITHER THE PANEL OR AT THE RECEPTACLE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved