| Date |
Text |
| 2016-09-15 12:07:46 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: PATIENT WING IMPROVEMENTS |
| | JOB ADDRESS: 5300 EAST AVE. |
| | DESCRIPTION: INTERIOR IMPROVEMENTS TO PATIENT ROOMS & |
| | UPGRADES TO VARIOUS CORRIDORS & OTHER AREAS |
| | MASTER PERMIT: 16090195 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | SHEET E2 |
| | 1. PANTRY 027- NEC 210.8: GFI PROTECTION REQUIRED FOR |
| | OUTLETS ON KITCHEN COUNTER. |
| | 2. EXISTING RESIDENT ROOMS, EXISTING PANTRIES 217 & |
| | 317, AND MED 011- NEC 210.8: GFI PROTECTION REQUIRED |
| | FOR OUTLETS WITHIN 6 FT. OF SINK. |
| | 3. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY |
| | CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN |
| | OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE |
| | INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD |
| | 90.1) |
| | SHEET E3 |
| | 1. EXIST COUNSEL 309, EXIST CORR. 024-THERE APPEARS TO |
| | BE A MISPLACED OR INCORRECTLY LABELED EXIT LIGHT |
| | 2. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT |
| | ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE |
| | DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL |
| | AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH |
| | EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2. |
| | THERE DOES NOT APPEAR TO BE DAYLIGHT ZONIFICATION. |
| | SHEET E5 |
| | 1. PANEL LD CIRCUIT 35 FOR THE EWC SHALL BE GFI |
| | PROTECTED AT EITHER THE PANEL OR AT THE RECEPTACLE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |