Plan Review Notes
Plan Review Notes For Permit 16090195
Permit Number 16090195
Review Stop B
Sequence Number 1
Notes
Date Text
2016-09-20 09:45:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090195
 ADD: 5300 EAST AVE.
 CONT: TRILLIUM CONSTRUCTION
 TEL: 561-296-0700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 20/2016
 ACTION: DENIED
  
 1) SHEET LS1 VERSES SHEET A1. LS 1 IN THE 200 & 300 1-2
 SLEEPING ROOM CARE SUITES THE PLANS SHOW A SMOKE RATED
 WALL BETWEEN THE CORRIDOR AND SLEEPING ROOMS. SHEET A1
 DOES NOT DEPICT THIS ON THE FLOOR PLAN DISCREPANCY IN
 PLANS, 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 CORRIDOR WALLS ARE TO BE CONSTRUCTED AS SMOKE
 PARTITIONS IN ACCORDANCE WITH 2014 FBC-B 710.4
 CONTINUITY.
  
 2) THE FLOOR PLAN SHEET LS1 AND SHEET A1. NEITHER SHOW
 SMOKE RATED WALLS FOR ROOMS 008 SOILED LINEN AND 009
 CENTRAL SUPPLY ROOM. THE ROOM FINISH SCHEDULE ON SHEET
 A1 INDICATES UNDER REMARKS: 0.060 INCH THICK WALL
 PROTECTION. FBC-B 509.4.2 PROTECTION. WHERE TABLE 509
 PERMITS AN AUTOMATIC SPRINKLER SYSTEM WITHOUT A FIRE
 BARRIER, THE INCIDENTAL USES SHALL BE SEPARATED FROM
 THE REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE
 OF RESISTING THE PASSAGE OF SMOKE. DOORS SHALL BE SELF-
 OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3.
  
 3) SHEET A1 UNDER THE HEADING OF ROOM FINISH SCHEDULE
 INDICATES ROOMS 218 & 318 AS WHEELCHAIR STORAGE BUT I
 DID NOT FIND THESE ROOMS IN THE 1-2 SUITE OF ROOMS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET A1 SHOWS THE ELEVATOR BEING ELIMINATED, PLEASE
 PROVIDE HOW WILL COMPLIANCE WITH 201.1.1 ACCESS. CODE
 VERTICAL ACCESSIBILITY BE ACHIEVED?
  
 5) SHEET A1 ROOMS 111-115 SHOW THE INSTALLATION OF NEW
 EXTERIOR DOORS, SHEET SHOWS DETAILS FOR THE NEW
 STOREFRONT SYSTEM BUT I COULD NOT FIND WHERE THE 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 6) PLEASE NOTE A SERIES 35H YKK AP AMERICA OUTSWING
 ENTRANCE DOORS TECHNICAL SHEETS WERE SUBMITTED, THEY DO
 NOT HAVE ANY INDICATION IF THEY ARE A FLORIDA APPROVAL
 OR A MIAMI-DADE NOA. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) THE SERIES 35H YKK AP AMERICA OUTSWING ENTRANCE
 DOORS ARE FOR DOUBLE DOORS ONLY NOT FOR SIDE LIGHTS AS
 DEPICTED ON SHEET A8 DETAIL F2. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1. FBC 107.3.4.1
 PRODUCT APPROVALS. COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31(C) PANEL WALLS: STOREFRONTS,
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8)SHEET A6 DETAIL B INDICATES A MICROWAVE SITTING ON A
 SHELF AT AN ELEVATION OF 4 FOOT 6 INCHES WHICH IS
 LOCATED ABOVE THE REACH RANGES. SEE 2014 FBC-ACCESS.
 CODE 308.2 FORWARD REACH , 308.3 SIDE REACH AND 309.3
 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR
 MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  