| Plan Review Notes For Permit 16090189 |
| Permit Number |
16090189 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-13 05:07:07 | 1) POOL SYSTEM FLOW RATE - THE FLOW IS NOTED AS 120 GPM | | | AT A TDH OF 30 BUT ACCORDING TO THE PUMP CURVE THE | | | MAXIMUM FLOW AT 30 TDH IS 110 GPM . THE MAXXIMUM GPM ON | | | THE CURVE IS SHOWN AS 120 GPM SO WHERE DOES THE 130 GPM | | | COME FROM? CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|