2016-11-29 07:10:092ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090159
 11/29/16
  
 1) SPECS HAVE BEEN SUBMITTED FOR THE CARRIER FX4D AIR
 HANDLER TO VERIFY CAPACITIES. PLEASE SUBMIT SPECS FOR
 THE 5-TON FB4C AIR HANDLER.
  
 2) THE AC CALCULATIONS ARE LISTING 18 OCCUPANTS FOR THE
 HOUSE. PLEASE REVIEW ACCA MANUAL J. INTERNAL GAINS
 CRITERIA FOR SIZING LOADS DETERMINE OCCUPANTS BASED ON
 THE NUMBER OF BEDROOMS PLUS ONE, WHICH WOULD BE 6 FOR
 THE MAIN HOUSE- PLEASE CORRECT.
  
 3) IF PROVIDING A FL. PRODUCT APPROVAL FOR CONDENSER
 ANCHORING CLIPS, PLEASE SUBMIT THE ENTIRE DOCUMENT
 INCLUDING THE COVER SHEET TO VERIFY- RULE 9N-3 FLORIDA
 DEPT. OF COMMUNITY AFFAIRS.
  