| 2016-11-28 17:10:15 | JOB PERMIT NUMBER: 16090159 |
| | JOB ADDRESS: 234 DESOTA RD (NEW RESIDENCE) |
| | WEST PALM BEACH FLORIDA 33405 |
| | DATE: NOVEMBER 28, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] NOT ADDRESSED, PROVIDE FPL AVAILABLE FAULT CURRENT |
| | LETTER & SHOW AIC CALCULATIONS TO VERIFY SHORT CIRCUIT |
| | RATING OF ELECTRICAL EQUIPMENT. FBC-R SECTIONS E3404.2 |
| | & E3404.3 |
| | |
| | 2] ADDRESSED |
| | |
| | 3] NOT ADDRESSED, PROVIDE A NEUTRAL LOAD CALCULATION |
| | SINCE YOUR LOWERING YOUR SERVICE FEEDER CONDUCTOR. |
| | FBC-R SECTION E3704.3 |
| | |
| | 4] ADDRESSED |
| | |
| | 5] ADDRESSED |
| | |
| | 6] NOT ADDRESSED, SHOW 42 CIRCUIT PANEL 1A & 1B ON THE |
| | ELECTRICAL FLOOR PLAN. FBC 107 |
| | |
| | 7] ADDRESSED |
| | |
| | 8] ADDRESSED |
| | |
| | 9] ADDRESSED |
| | |
| | 10] NOT ADDRESSED, PLEASE LABEL CIRCUIT DESIGNATION ON |
| | THE FLOOR PLAN TO MATCH PANEL SCHEDULE. FBC 107 |
| | |
| | 11] ADDRESSED |
| | |
| | 12] ADDRESSED |
| | |
| | 13] ADDRESSED |
| | |
| | 14] SEMI ADDRESSED, CLARIFY SMOKE/CARBON ALARM DEVICE |
| | TO BE LISTED FOR INSTALLATION NEAR COOKING APPLIANCES |
| | WITH A SILENCEABLE FEATURE OR REMOVE DEVICE FROM THIS |
| | LOCATION. NFPA 72 SECTION 29.8.3.4 |
| | |
| | 15] ADDRESSED |
| | |
| | 16] ADDRESSED |
| | |
| | 17] FEEL FREE TO CONTACT ME SHOULD YOU HAVE QUESTIONS |
| | OR CONCERNS |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 2ND REVIEW FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |