| Plan Review Notes For Permit 16090159 |
| Permit Number |
16090159 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-17 12:11:24 | 1ST REVIEW FBC-2014 RESDIENTIAL MECHANICAL | | | PERMIT #16090159 | | | 10/17/16 | | | | | | 1) THE PLANS SHOW THE TOTAL SUPPLY CFMS EXCEEDING THE | | | CAPACITIES OF THE SELECTED SYSTEMS: THE 2095 CFMS SHOWN | | | ON THE 1ST FLOOR WOULD EXCEED THE CAPACITIY OF AC-1 | | | WHICH IS A 4-TON SYSTEM, AND THE 1610 CFMS SHOWN ON THE | | | 2ND FLOOR WOULD EXCEED THE CAPACITY OF AC-2 WHICH IS A | | | 3-TON SYSTEM. | | | | | | 2) PLEASE UPDATE THE CODE REFERENCE AND SECTION NUMBER | | | FOR THE C/U TIE DOWN. | | | | | | 3) REFER TO TABLE M1507.4 RESIDENTIAL AND PROVIDE A | | | KITCHEN EXHAUST SYSTEM AND THE EXHAUST VENTILATION | | | RATE. PROVIDE A SUBMITTAL AND EQUIPMENT SCHEDULE FOR | | | THE RANGE HOOD IF APPLICABLE- SEE SECTION M1503. | | | | | | 4) THE ENERGY FORM R405-2014 IS LACKING THE OWNER'S | | | NAME, OWNER'S SIGNATURE, THE JURISDICTION NUMBER, AND | | | THE COMPLETED AIR BARRIER AND INSULATION CHECKLIST. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|