Plan Review Notes
Plan Review Notes For Permit 16090159
Permit Number 16090159
Review Stop E
Sequence Number 1
Notes
Date Text
2016-09-27 09:20:42INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 2. PLEASE NOTE THAT THE ELECTRICAL SERVICE SHOWN IS NOT
 A TYPICAL FIELD INSTALLATION. CLARIFY IF THERE ARE 2
 -150AMP MAIN DISCONNECTS INSTEAD OF 1- 300AMP.
 3. SHOW SERVICE CONDUCTORS. FBC RES E3603
 4. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS, GENERATOR AND POOL. FBC
 107.3.5
 5. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 6. SHOW ON FLOOR PLAN LOCATION OF SERVICE EQUIPMENT.
 LABEL EQUIPMENT AS RATED FOR SERVICE ENTRANCE AND
 PROPER NEMA 3R RATING. FBC 107.3.5
 7. SHOW ALL EXTERIOR RECEPTACLE AT REAR PROTECTED BY
 GFCI DEVICE. FBC RES E3902.3
 8. RECEPTACLE AT WALL SPACE IN BAR AREA WITHIN 6FT OF
 SINK TO BE LABELED AS GFCI PROTECTED. FBC RES E3902.7
 9. SHOW JACUZZI AND GARAGE DOOR OPENER DEVICES TO BE
 PROTECTED BY GFCI BREAKER TO BE READILY ACCESSIBLE.
 LOADS FOR THESE ARE NOT REFLECTED ON PANEL SCHEDULES.
 10. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE
 PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE
 HOUSE IT?S SERVICING. SHOW ON PANEL SCHEDULE. GENERAL
 LIGHTING DOES NOT MEET THESE REQUIREMENTS. EXAMPLE,
 LABEL BEDROOM 1, BEDROOM 2 ETC.?NEC 408.4 FIELD ID
 REQUIRED. FBC 107.3.5
 11. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 12. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR
 DINING ROOM RECEPTACLES AND BATHROOM RECEPTACLES. FBC
 RES E3703.2 AND 4
 13. BRANCH CIRCUIT CONDUCTOR SIZE SHOWN FOR POOL PUMP
 EQUIP, ALL AHU UNITS ARE UNDERSIZED PER NEC 310.15B16
 TABLE OF AMPACITIES
 14. SHOW ALL SMOKE DETECTOR OUTSIDE OF BEDROOMS TO BE
 CO(CARBON MONOXIDE) PER FBC RES 315, MAINTAIN REQUIRED
 DISTANCES FROM KITCHEN APPLIANCES.
 15. SHOW ATTIC ACCESS LIGHTING ON PLANS. FBC 107.3.5
 16. PLEASE TRANSFER GENERAL ELECTRICAL NOTES ON FIRST
 SHEET A1 TO SHEET A12. FBC 107.3.5
 17. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  