| 2016-09-27 09:20:42 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA RES BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND |
| | LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC |
| | RATINGS. FBC 107.3.5 |
| | 2. PLEASE NOTE THAT THE ELECTRICAL SERVICE SHOWN IS NOT |
| | A TYPICAL FIELD INSTALLATION. CLARIFY IF THERE ARE 2 |
| | -150AMP MAIN DISCONNECTS INSTEAD OF 1- 300AMP. |
| | 3. SHOW SERVICE CONDUCTORS. FBC RES E3603 |
| | 4. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS |
| | FOR LOW VOLTAGE SYSTEMS, GENERATOR AND POOL. FBC |
| | 107.3.5 |
| | 5. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE |
| | PER FBC RES E3609.3 |
| | 6. SHOW ON FLOOR PLAN LOCATION OF SERVICE EQUIPMENT. |
| | LABEL EQUIPMENT AS RATED FOR SERVICE ENTRANCE AND |
| | PROPER NEMA 3R RATING. FBC 107.3.5 |
| | 7. SHOW ALL EXTERIOR RECEPTACLE AT REAR PROTECTED BY |
| | GFCI DEVICE. FBC RES E3902.3 |
| | 8. RECEPTACLE AT WALL SPACE IN BAR AREA WITHIN 6FT OF |
| | SINK TO BE LABELED AS GFCI PROTECTED. FBC RES E3902.7 |
| | 9. SHOW JACUZZI AND GARAGE DOOR OPENER DEVICES TO BE |
| | PROTECTED BY GFCI BREAKER TO BE READILY ACCESSIBLE. |
| | LOADS FOR THESE ARE NOT REFLECTED ON PANEL SCHEDULES. |
| | 10. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE |
| | PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE |
| | HOUSE IT?S SERVICING. SHOW ON PANEL SCHEDULE. GENERAL |
| | LIGHTING DOES NOT MEET THESE REQUIREMENTS. EXAMPLE, |
| | LABEL BEDROOM 1, BEDROOM 2 ETC.?NEC 408.4 FIELD ID |
| | REQUIRED. FBC 107.3.5 |
| | 11. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO |
| | INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS. |
| | 12. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR |
| | DINING ROOM RECEPTACLES AND BATHROOM RECEPTACLES. FBC |
| | RES E3703.2 AND 4 |
| | 13. BRANCH CIRCUIT CONDUCTOR SIZE SHOWN FOR POOL PUMP |
| | EQUIP, ALL AHU UNITS ARE UNDERSIZED PER NEC 310.15B16 |
| | TABLE OF AMPACITIES |
| | 14. SHOW ALL SMOKE DETECTOR OUTSIDE OF BEDROOMS TO BE |
| | CO(CARBON MONOXIDE) PER FBC RES 315, MAINTAIN REQUIRED |
| | DISTANCES FROM KITCHEN APPLIANCES. |
| | 15. SHOW ATTIC ACCESS LIGHTING ON PLANS. FBC 107.3.5 |
| | 16. PLEASE TRANSFER GENERAL ELECTRICAL NOTES ON FIRST |
| | SHEET A1 TO SHEET A12. FBC 107.3.5 |
| | 17. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| | QUESTIONS OR CONCERNS. |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |