2016-09-20 18:13:06NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
 NOTE: THIS MAY DONE LATER WHEN THE PERMIT IS READY TO
 BE ISSUED.
  
 2- PROVIDE SITE DRAINAGE PLAN AS REQUIRED BY SEC.
 R401.3 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- SHEET A1: GARAGE DOOR DESIGN PRESSURES SHOWN ON THE
 DATA & DESIGN PRESSURE SCHEDULE ARE TOO LOW BASED ON
 THE ADJUSTMENT COEFFICIENT (1.36) AND TABLE R301.2(4)
 FBC-RESIDENTIAL. REVISE AS REQUIRED OR PROVIDE COMPLETE
 ENGINEERING CALCULATIONS.
  
 4- SETBACK DIMENSIONS SHOWN ON THE SURVEY SUBMITTED
 DON'T MATCH SETBACK DIMENSIONS SHOWN ON SHEET A2.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- SHEET A3 AND S1 SHOWS 1.5" DROP FROM THE FINISH
 CONCRETE SLAB TO THE FINISHED GRADE. PROVIDE COMPLETE
 INFORMATION SHOWING COMPLIANCE WITH THE CLEARANCE FOR
 TERRMITE INSPECTION SEC. R318.7 AND HEIGHT ABOVE
 FINISHED GRADE SEC. R404.1.6 FBC-RESIDENTIAL, 5TH
 EDITION (2014). REVISE AS REQUIRED.
  
 6- NEED TO SPECIFY ATTIC ACCESS BY THE MASTER BATHROOM,
 EAST GARAGE AREA AND REAR LANAI AS REQUIRED BY SEC.
 R807 FBC-RESIDENTIAL.
  
 7-GARAGE DOOR LEADING TO THE MAIN HOUSE NEEDS TO HAVE A
 SELF CLOSING DEVICE AS REQUIRED BY SEC. R302.5.1
 FBC-RESIDENTIAL.
  
 8- GARAGE STRUCTURAL BUCK DETAIL DETAIL 1/A11: PROVIDE
 COMPLETE SPECIFICATIONS FOR FASTENER TYPE, SIZE AND
 SPACING. STRUCTURAL BUCK ATTACHMENT IS THE
 RESPONSIBILITY OF THE DESIGNER OF RECORD NOT THE GARAGE
 DOOR MANUFACTURER. SEC. R301.1 FBC-RESIDENTIAL.
  
 9-PROVIDE SPRAY FOAM INSULATION ICC EVALUATION REPORT
 SPECIFIED ON DETAIL 1/S4 TO SHOW COMPLIANCE WITH SEC.
 R316 FBC-RESIDENTIAL. NOTE: REPORT TO BE REVIEWED AND
 APPROVED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL TO
 THIS OFFICE.
  
 10- PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THE
 STUCCO SOFFIT SPECIFIED ON DETAIL 1/S4 SHOWING
 COMPLIANCE WITH SEC. R703.1.3 FBC-RESIDENTIAL.
  
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR:
 A) THE-LANAI CEILING CONSTRUCTION. SEC. R301.1
 FBC-RESIDENTIAL.
  
 B) THE ENTRY BALCONIES CEILING CONSTRUCTION. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 12- DETAIL 1/S4: PROVIDE COMPLETE INFORMATION SHOWING
 COMPLIANCE WITH THE CLEARANCE FOR TERMITE INSPECTION
 SEC. R318.7 AND HEIGHT ABOVE FINISHED GRADE SEC.
 R404.1.6 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 13- CABANA FOUNDATION PLANS SHOWN ON SHEET S1 IS
 MISSING THE FOOTING. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL.
  
 14- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF GABLE END TRUSS AND BALCONY SOFFIT AS
 SHOWN ON DETAIL 2/S4. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL.
  
 15- WALL SECTIONS ON SHEET S4: SPECIFY FIREBLOCKING AS
 REQUIRED BY SEC. R302.11 FBC-RESIDENTIAL.
  
 16- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 SECOND FLOOR DRAFSTOPPING AS REQUIRED BY SEC. R302.12
 FBC-RESIDENTIAL.
  
 17- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 1 HOUR FIRE RATED UNDERSIDE OF THE CABANA SOFFIT AS
 REQUIRED BY TABLE R302.1(1) FBC-RESIDENTIAL.
  
 18- STRUCTURAL ENGINEER WHO SIGNED AND SEALED THE
 STRUCTURAL DRAWINGS NEED TO UPDATE THE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION (#9318) WITH DBPR AS
 REQUIRED BY FAC 61G15-23.00219.
  
 19- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF THE STAIRWAY SHOWING
 COMPLIANCE WITH SEC. R311.7 FBC-RESIDENTIAL.
  
 20- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF ALL HANDRAILS, AND
 GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE LOADS OF
 TABLE R301.5 FBC-RESIDENTIAL AND ALL THE REQUIREMENTS
 OF SEC. R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
  
 21- ENERGY CALCULATIONS SUBMITTED:
 MAIN HOUSE:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME AND JURISDICTION #. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) CLEARLY PROVIDE THE NAME OF THE INDIVIDUAL
 COMPLETING THE COMPLIANCE REPORT AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) OWNER/AGENT NEEDS TO CERTIFY AT BOTTOM OF FORM AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 D) CLARIFY WHY THERE ARE 18 OCCUPANTS SPECIFIED ON PAGE
 2 OF 5. TYPICALLY, 18 PEOPLE IS NOT AN USUAL NUMBER OF
 PEOPLE FOR A SINGLE FAMILY RESIDENCE. WHAT'S THE
 PROPOSED USE OF THIS SINGLE FAMILY RESIDENCE. PROVIDE
 DOCUMENTATION THAT VERIFIES THE NUMBER OF PEOPLE
 SPECIFIED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 E) INSULATION R-VALUE AND TYPE SHOWN ON THE CEILING
 INFORMATION ON PAGE 3 OF 5 DOESN'T MATCH INFORMATION
 SHOWN ON ITEM #10 OF PAGE 1 AND PLANS SUBMITTED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) DOORS INFORMATION SHOWN ON PAGE 3 OF 5 DOESN'T MATCH
 INFORMATION SHOWN ON PLANS AND PRODUCT APPROVALS
 SUBMITTED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014). NOTE: DOOR WITH GLAZING NEEDS TO BE
 INCLUDED IN THE WINDOWS AREA.
  
 G) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 H) COMPLETE THE INSPECTION CHECKLIST TABLE 402.4.1.1
 SUBMITTED. SEC. R405.4.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
  
 CABANA:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME AND JURISDICTION #. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) CLEARLY PROVIDE THE NAME OF THE INDIVIDUAL
 COMPLETING THE COMPLIANCE REPORT AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) OWNER/AGENT NEEDS TO CERTIFY AT BOTTOM OF FORM AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 D) INSULATION R-VALUE AND TYPE SHOWN ON THE CEILING
 INFORMATION ON PAGE 2 OF 4 DOESN'T MATCH INFORMATION
 SHOWN ON ITEM #10 OF PAGE 1 AND ON PLANS SUBMITTED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 E) THERE IS NO KITCHEN IN THE CABANA. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 F) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) COMPLETE THE INSPECTION CHECKLIST TABLE 402.4.1.1
 SUBMITTED. SEC. R405.4.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 NOTE: LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT
 USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 22- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE. PROVIDE COMPLETE INFORMATION FOR THE
 SPECIFIC ROOF TILE TO BE INSTALLED. ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE FL7849-R9 WAS SUBMITTED.
 ALSO, NEED TO PROVIDE TWO COPIES. ONLY ONE WAS
 SUBMITTED.
  
 B) PEEL-N-STICK ROOF TILE UNDERLAYMENT AS SPECIFIED ON
 DRAWINGS.
  
 C) BALCONIES UNDERLAYMENT THAT IS DESIGNED TO RECEIVE
 TILE OR MARBLE AS SPECIFIED ON THE FINISH SCHEDULE ON
 SHEET A7. NOTE: CLEARLY IDENTIFY ON PRODUCT APPROVAL
 SPECIFIC ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
  
 D) CASEMENT WINDOWS AS SPECIFIED ON PLANS. NEED PRODUCT
 APPROVAL THAT COVERS WINDOW HEIGHT SPECIFIED FOR DOUBLE
 WINDOWS "A" AND "B". NOA 15-0420.11 SUBMITTED DOESN'T
 COVER THOSE SIZES.
  
 E) GARAGE DOORS. NOTE: COORDINATE DESIGN PRESSURES WITH
 REVISED DESIGN PRESSURES REQUIRED ON ITEM # 3 ABOVE.
  
 F) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 G) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR LIST THE FLORIDA PRODUCT APPROVAL NUMBER
 NEXT TO EACH SPECIFIED CONNECTOR.
  
 23- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 24- ENGINEER OF RECORD TO CLEARLY SPECIFY ALL LIVE
 LOADS, DEAD LOAD ( SECOND FLOOR, BALCONIES, ROOF, ETC).
 SEC.R301.1 FBC-RESIDENTIAL. AND INCLUDE THE ATTIC LIVE
 LOADS AS REQUIRED BY NOTES "B" AND "G" OF TABLE R301.5
 FBC-RESIDENTIAL.
  
 25- STRUCTURAL PLANS AND TRUSS PLANS NEED TO BE
 COORDINATED. FRAMING PLANS DON'T MATCH. THERE ARE AREAS
 WHERE TRUSS PLANS CALL FOR BEARING WALLS, WHILE
 STRUCTURAL ENGINEER PLANS CALL FOR GIRDER TRUSSES.
 NOTE: ALSO COORDINATE ALL BEARING WALLS, LOAD BEARING
 POINTS AND RESPECTIVE FOOTINGS. SEC. R301.1
 FBC-RESIDENTIAL. REVISE PLANS TO MATCH.
  
 26- TRUSS PACKAGE SUBMITTED:
 A) TRUSS ENGINEER TO SIGN AND SEAL TRUSS LAYOUT AS
 REQUIRED BY FAC 61G15-23.002.
 B) TRUSS PACKAGE COVER PAGE TO HAVE ENGINEER'S ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. IT LOOKS
 LIKE SIGNATURE ON COVER R PAGE SUBMITTED IS A COPY.
 C) TRUSS PACKAGE COVER PAGE TO HAVE THE INFORMATION OF
 THE STRUCTURAL ENGINEER OF RECORD AS REQUIRED BY FAC
 61G15-31.003.
 D) EACH OF THE DRAWINGS OF THE TRUSS PACKAGE NEED TO
 HAVE THE TITLE BLOCK OF THE TRUSS ENGINEER AS REQUIRED
 BY FAC 61G15-31.003.
 E) TRUSS PACKAGE TO BE REVIEWED AND APPROVED BY THE
 ENGINEER OF RECORD AS REQUIRED BY FAC 61G15-30.005.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE TO EXPEDITE REVIEW PROCESS.
  