| Plan Review Notes For Permit 16090150 |
| Permit Number |
16090150 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-12 14:13:06 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT REVISION #16090150 | | | 9/12/16 | | | | | | 1) FIRE DAMPERS MISSING FOR THE RETURN AIR DUCTS | | | PENETRATING THE FIRE-RATED CONTROL ROOM WALLS. | | | | | | 2) THE REVISED DRAWING SHOWS THE EF-1 REMOVED FROM THE | | | CHEMICAL STORAGE CLOSET. THIS IS A REQUIRED EXHAUST FAN | | | PER THE APPROVED PLANS. | | | | | | 2) CLARIFY THE PURPOSE OF THE NEW CLOSET 110. IS THIS | | | ALSO A CHEMICAL STORAGE CLOSET? PLEASE NOTE THAT RETURN | | | AIR FROM A CLOSET IS PROHIBITED- SEE SECTION 918.6. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|