2016-09-12 14:13:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT REVISION #16090150
 9/12/16
  
 1) FIRE DAMPERS MISSING FOR THE RETURN AIR DUCTS
 PENETRATING THE FIRE-RATED CONTROL ROOM WALLS.
  
 2) THE REVISED DRAWING SHOWS THE EF-1 REMOVED FROM THE
 CHEMICAL STORAGE CLOSET. THIS IS A REQUIRED EXHAUST FAN
 PER THE APPROVED PLANS.
  
 2) CLARIFY THE PURPOSE OF THE NEW CLOSET 110. IS THIS
 ALSO A CHEMICAL STORAGE CLOSET? PLEASE NOTE THAT RETURN
 AIR FROM A CLOSET IS PROHIBITED- SEE SECTION 918.6.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER