| Date |
Text |
| 2016-09-16 09:56:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE APPEARS TO BE A/C DUCT WORK PASSING TROUGH |
| | FIRE RATED WALLS. |
| | |
| | PER THE FLORIDA FIRE PREVENTION CODE NFPA 1 AND 101, |
| | 5TH EDITION: |
| | |
| | CHAPTER 8 FEATURES OF FIRE PROTECTION |
| | |
| | 8.3.5.7 OPENINGS FOR AIR-HANDLING DUCTWORK. OPENINGS IN |
| | FIRE BARRIERS FOR AIR-HANDLING DUCTWORK OR AIR MOVEMENT |
| | SHALL BE PROTECTED IN ACCORDANCE WITH 9.2.1. |
| | |
| | 8.5.5.5 ACCESS AND IDENTIFICATION. ACCESS TO THE |
| | DAMPERS SHALL BE PROVIDED FOR INSPECTION, TESTING, AND |
| | MAINTENANCE. THE ACCESS OPENINGS SHALL NOT REDUCE THE |
| | FIRE RESISTANCE RATING OF THE FIRE BARRIER ASSEMBLY. |
| | |
| | 9.2 HEATING, VENTILATING, AND AIR-CONDITIONING. |
| | |
| | 9.2.1 AIR-CONDITIONING, HEATING, VENTILATING DUCTWORK, |
| | AND RELATED EQUIPMENT. AIR-CONDITIONING, HEATING, |
| | VENTILATING DUCTWORK, AND RELATED EQUIPMENT SHALL BE IN |
| | ACCORDANCE WITH NFPA 90A, STANDARD FOR THE INSTALLATION |
| | OF AIR-CONDITIONING AND |
| | VENTILATING SYSTEMS, OR NFPA 90B, STANDARD FOR THE |
| | INSTALLATION OF WARM AIR HEATING AND AIR-CONDITIONING |
| | SYSTEMS, AS APPLICABLE, UNLESS SUCH INSTALLATIONS ARE |
| | APPROVED EXISTING INSTALLATIONS, WHICH SHALL BE |
| | PERMITTED TO BE CONTINUED IN SERVICE. |
| | |
| | |
| | |
| | 2) ENSURE THE FIRE RATED WALL IS IDENTIFIED AS |
| | REQUIRED. |
| | |
| | 8.3.2.4 EACH NEW FIRE WALL, FIRE BARRIER, FIRE |
| | PARTITION, SMOKE BARRIER, SMOKE PARTITION, OR ANY OTHER |
| | NEW WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES WITH THE |
| | WORDING, ?FIRE AND SMOKE BARRIER ? PROTECT ALL |
| | OPENINGS,? OR SIMILAR LANGUAGE. SUCH SIGNS OR |
| | STENCILING SHALL BE IN 4 INCH HIGH LETTERS, ? INCH |
| | STROKE, AND NOT MORE THAN 15 FEET ON-CENTER. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |