| 2016-09-15 09:37:55 | PLEASE NOTE THAT THE QUALITY OF PLANS SHEETS ARE FADING | | | DUE TO INK DEFICIENCY, MAKING IT NON-LIGIBLE. REPRINT | | | AND SUBMIT NEW. SEE PLANS. | | | | | | PROVIDE PER NEC 702.7-SIGNS- A GENERAL NOTE ON RISER | | | DIAGRAM TO INDICATE SINAGE REQUIREMENTS FOR THE | | | OPTIONAL STANDY SYSTEM. | | | | | | ADDRESS MECHANICAL COMMENT REGARDING EX FAN STORAGE | | | ROOM | | | | | | UPGRADED 200A NOW SHOWN FOR UNTT 120, SHOWS A THE | | | NEUTRAL CONDUCTOR REDUCTION IN SIZE. EITHER PROVIDE | | | NEUTRAL CALCULATION OR SHOW AT THE SAME SIZE OF | | | UNGROUNDED CONDUCTORS. NEC 220.61 | | | ALSO THE UPGRADE TO UNIT IMPACTS THE EXISTING SERVICE | | | SIZE SHOWN AT 800AMPS. BY INCREASING LOADS PLEASE | | | PROVIDE A REVISED CALCULATION OF SERVICE TO VERIFY THAT | | | THE EXISTING SERVICE WILL HANDLE THE INCREASE TO 200AMP | | | SERVICE. FBC 107.3.5 | | | | | | | | | VAL PEREZ | | | | | | |
|