2016-09-15 09:37:55PLEASE NOTE THAT THE QUALITY OF PLANS SHEETS ARE FADING
 DUE TO INK DEFICIENCY, MAKING IT NON-LIGIBLE. REPRINT
 AND SUBMIT NEW. SEE PLANS.
  
 PROVIDE PER NEC 702.7-SIGNS- A GENERAL NOTE ON RISER
 DIAGRAM TO INDICATE SINAGE REQUIREMENTS FOR THE
 OPTIONAL STANDY SYSTEM.
  
 ADDRESS MECHANICAL COMMENT REGARDING EX FAN STORAGE
 ROOM
  
 UPGRADED 200A NOW SHOWN FOR UNTT 120, SHOWS A THE
 NEUTRAL CONDUCTOR REDUCTION IN SIZE. EITHER PROVIDE
 NEUTRAL CALCULATION OR SHOW AT THE SAME SIZE OF
 UNGROUNDED CONDUCTORS. NEC 220.61
 ALSO THE UPGRADE TO UNIT IMPACTS THE EXISTING SERVICE
 SIZE SHOWN AT 800AMPS. BY INCREASING LOADS PLEASE
 PROVIDE A REVISED CALCULATION OF SERVICE TO VERIFY THAT
 THE EXISTING SERVICE WILL HANDLE THE INCREASE TO 200AMP
 SERVICE. FBC 107.3.5
  
  