| Plan Review Notes For Permit 16090150 |
| Permit Number |
16090150 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-12 12:32:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A MEANS OF EGRESS DOOR FOR WORKROOM 109, FBC | | | 1014.2(1). | | | | | | 2. SHEET A2.3 DETAIL B2, CONSTRUCTION AND COMPLIANCE | | | FOR THE UL DETAIL IS NOT CLEAR. THE WALL IS OFFSET; | | | STRUCTURAL SUPPORT OF THE WALL AS DRAWN IS NOT CLEAR. | | | CONFIRM WITH U.L. THAT THIS WALL DETAIL CAN BE USED IN | | | A HORIZONTAL (CEILING) APPLICATION. CONFIRM WITH U.L. | | | THAT THE WALL CAN BE CONSTRUCTED IN AN OFFSET MANNER | | | AND MAINTAIN THE REQUIRED RATING. | | | | | | COMPLETE THE DETAIL BY EITHER PROVIDING THE OPTION | | | SELECTED OR ALL OF THE OPTIONS, FBC 107. | | | | | | | | | |
|