| 2016-10-11 16:45:18 | REVISION REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: (THE COMMENTS |
| | FROM THE PREVIOUS REVIEW HAVE NOT BEEN ADDRESSED) |
| | |
| | 1) THE REVISED DUCT WORK IS UPSIDE DOWN ON THE PLANS. |
| | PLEASE CORRECT. FBC 107.2.1.4 |
| | |
| | 2) THE REVISED DUCT WORK SHOWN ON THE PLAN IS TOO LIGHT |
| | IN SOME AREAS MAKING IT ILLEGIBLE AND THE CONTRAST IS |
| | NOT SUITABLE TO BE COPIED INTO THE RECORDS. FBC |
| | 107.2.1.4 |
| | |
| | 3) THE SIZE OF THE MECHANICAL EQUIPMENT HAS BEEN |
| | CHANGED. SUBMIT REVISED ENERGY COMPLIANCE FORMS AND |
| | LOAD CALCULATIONS WITH THE REQUIRED SIGNATURES. FBC |
| | ENERGY CONSERVATION R101.5.1 & FBCR M1401.3 |
| | |
| | 4) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 5) THE ARCHITECT'S NAME AND LICENSE NUMBER IS LISTED IN |
| | THE TITLE BLOCK, THEREFORE, THE PLANS ARE REQUIRED TO |
| | BE SIGNED AND SEALED BY HIM. FLORIDA STATUTES 481 |
| | |
| | 6) ON THE ORIGINAL APPROVED PLANS SYSTEM 1 IS HALF A |
| | TON LARGER THAN SYSTEM 2. ON THE REVISED PLANS SYSTEM 2 |
| | IS ONE TON LARGER THAN SYSTEM 1 AND THE AREA THAT EACH |
| | ONE SERVICES HAS NOT CHANGED. PLEASE CLARIFY. FBC |
| | 107.2.1 |
| | |
| | 7) THE EQUIPMENT SIZING / LOAD CALCULATIONS THAT WERE |
| | ORIGINALLY SUBMITTED AND APPROVED HAVE A TOTAL COOLING |
| | LOAD OF 47,983 BTUH OR 4.00 TONS ( BASED ON SENSIBLE |
| | AND LATENT ). THE REVISED PLANS AND ENERGY FORMS HAVE A |
| | TOTAL COOLING LOAD OF 56,800 BTUH ( 57,600 BTUH ON THE |
| | HVAC PLAN) OR 5.00 TONS. THE PREVIOUSLY APPROVED LOAD |
| | CALCULATIONS DO NOT SUPPORT THE 5.00 TON TOTAL LOAD. |
| | FBC ENERGY CONSERVATION SECTION R403.6.1.1 |
| | |
| | 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |