| Plan Review Notes For Permit 16090134 |
| Permit Number |
16090134 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-09-08 10:23:58 | REVISION REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE REVISED DUCT WORK IS UPSIDE DOWN ON THE PLANS. | | | PLEASE CORRECT. FBC 107.2.1.4 | | | | | | 2) THE REVISED DUCT WORK SHOWN ON THE PLAN IS TOO LIGHT | | | IN SOME AREAS MAKING IT ILLEGIBLE AND THE CONTRAST IS | | | NOT SUITABLE TO BE COPIED INTO THE RECORDS. FBC | | | 107.2.1.4 | | | | | | 3) THE SIZE OF THE MECHANICAL EQUIPMENT HAS BEEN | | | CHANGED. SUBMIT REVISED ENERGY COMPLIANCE FORMS AND | | | LOAD CALCULATIONS WITH THE REQUIRED SIGNATURES. FBC | | | ENERGY CONSERVATION R101.5.1 & FBCR M1401.3 | | | | | | 4) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 5) THE ARCHITECT'S NAME AND LICENSE NUMBER IS LISTED IN | | | THE TITLE BLOCK, THEREFORE, THE PLANS ARE REQUIRED TO | | | BE SIGNED AND SEALED BY HIM. FLORIDA STATUTES 481 | | | | | | 6) ON THE ORIGINAL APPROVED PLANS SYSTEM 1 IS HALF A | | | TON LARGER THAN SYSTEM 2. ON THE REVISED PLANS SYSTEM 2 | | | IS ONE TON LARGER THAN SYSTEM 1 AND THE AREA THAT EACH | | | ONE SERVICES HAS NOT CHANGED. PLEASE CLARIFY. FBC | | | 107.2.1 | | | |
|