Plan Review Notes
Plan Review Notes For Permit 16090134
Permit Number 16090134
Review Stop M
Sequence Number 2
Notes
Date Text
2016-09-08 10:23:58REVISION REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE REVISED DUCT WORK IS UPSIDE DOWN ON THE PLANS.
 PLEASE CORRECT. FBC 107.2.1.4
  
 2) THE REVISED DUCT WORK SHOWN ON THE PLAN IS TOO LIGHT
 IN SOME AREAS MAKING IT ILLEGIBLE AND THE CONTRAST IS
 NOT SUITABLE TO BE COPIED INTO THE RECORDS. FBC
 107.2.1.4
  
 3) THE SIZE OF THE MECHANICAL EQUIPMENT HAS BEEN
 CHANGED. SUBMIT REVISED ENERGY COMPLIANCE FORMS AND
 LOAD CALCULATIONS WITH THE REQUIRED SIGNATURES. FBC
 ENERGY CONSERVATION R101.5.1 & FBCR M1401.3
  
 4) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 5) THE ARCHITECT'S NAME AND LICENSE NUMBER IS LISTED IN
 THE TITLE BLOCK, THEREFORE, THE PLANS ARE REQUIRED TO
 BE SIGNED AND SEALED BY HIM. FLORIDA STATUTES 481
  
 6) ON THE ORIGINAL APPROVED PLANS SYSTEM 1 IS HALF A
 TON LARGER THAN SYSTEM 2. ON THE REVISED PLANS SYSTEM 2
 IS ONE TON LARGER THAN SYSTEM 1 AND THE AREA THAT EACH
 ONE SERVICES HAS NOT CHANGED. PLEASE CLARIFY. FBC
 107.2.1
  