| Plan Review Notes For Permit 16090110 |
| Permit Number |
16090110 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-08 03:45:06 | 1) INDICATE ON THE BOTH SETS OF PLANS IF THE GAS METER | | | THAT IS SHOWN IS AN ADDITIONAL NEW METER OR THE | | | EXISTING METER. IF THESE LANTERNS ARE BEING SUPPLIED BY | | | THE EXISTING METER, THEN A NEW GAS RISER SHALL BE | | | SUBMITTED SHOWING THE ENTIRE BTU LOAD AND ALL OF THE | | | EXISTING PIPE SIZES. THE ADDITIONAL LOAD OF 154,000 | | | BTU'S MAY REQUIRE SOME OF THE EXISTING PIPING TO BE | | | INCREASED IN SIZE TO ACCOMMODATE THE ENTIRE LOAD ON THE | | | SYSTEM. 2014 FGC SEC.401.4. I HAVE INCLUDED COPIES OF | | | THE PREVIOUSLY PERMITTED GAS PIPING SYSTEM FOR YOUR | | | PURVIEW. | | | 2) THE MAXIMUM BTU LOAD ON 1/2 INCH PE PIPE AT 90 FEET | | | AND LESS THAN 2 PSI PER TABLE 402.4 (21) IS 61,000 | | | BTU'S. THE PLAN SHOWS 4 LANTERNS ON A 1/2 INCH PE LINE | | | AND A TOTAL OF 88,000 BTU'S. INCREASE THE PIPE SIZE AS | | | NEEDED. | | | 3) SIZE THE LINE CONNECTING TO THE CONSUMER'S SIDE OF | | | THE GAS METER. INDICATE THE TYPE OF PIPE. WPB AMEND. TO | | | FBC SEC.107.2.1. | | | 4) INDICATE THE TYPE OF PIPE AND PIPE SIZE FOR THE STUB | | | UPS FOR THE LANTERNS. | | | 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE | | | LANTERNS. THE LANTERNS SHALL BE LISTED AND LABELED IN | | | ACCORDANCE WITH 2014 FGC SEC. 301.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|