| Plan Review Notes For Permit 16090104 |
| Permit Number |
16090104 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-07 15:34:41 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PROVIDE ELECTRIC SERVICE RISER WITH WIRE SIZES, | | | CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE LOAD | | | CALCULATIONS, PANEL SCHEDULES AND SHOW MATCHING | | | CIRCUITS ON FLOOR PLAN.FBC- 107.3.5.3 | | | | | | 2] ALL RECEPTACLE OUTLETS IN THE LAUNDRY ROOM SHALL BE | | | GFCI PROTECTED. NEC 210.8(A) | | | | | | 3] ALL NEWLY INSTALLED RECEPTACLES SHALL BE | | | TAMPER-RESISTANT IN ACCORDANCE WITH NEC 406.12 |
|