2016-09-07 15:34:41REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE ELECTRIC SERVICE RISER WITH WIRE SIZES,
 CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW MATCHING
 CIRCUITS ON FLOOR PLAN.FBC- 107.3.5.3
  
 2] ALL RECEPTACLE OUTLETS IN THE LAUNDRY ROOM SHALL BE
 GFCI PROTECTED. NEC 210.8(A)
  
 3] ALL NEWLY INSTALLED RECEPTACLES SHALL BE
 TAMPER-RESISTANT IN ACCORDANCE WITH NEC 406.12