| Plan Review Notes For Permit 16090016 |
| Permit Number |
16090016 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-06 05:59:24 | 1) SUBMIT TWO COPIES OF A PLAN THAT CLEARLY REFLECTS | | | THE SCOPE OF WORK TO BE DONE. ONLY ONE COPY OF A PLAN | | | HAS BEEN SUBMITTED AND THERE IS NO NOTE ON THE PLAN AS | | | TO WHAT THE SCOPE OF WORK IS TO BE DONE.. WPB AMEND. TO | | | FBC SEC. 107.1. | | | 2) INDICATE THE SIZE OF THE WATER SERVICES ON THE PLAN. | | | 3) INDICATE ON THE PLAN IF THERE IS AN EXISTING | | | BACKFLOW PREVENTION DEVICE ON EACH WATER SERVICE. IF | | | SO, INDICATE THE TYPE OF DEVICE. IF NOT, AN APPROVED | | | LEAD FREE DEVICE MAY BE REQUIRED ON EACH WATER SERVICE | | | PER THE CITY OF WPB CROSS-CONNECTION CONTROL MANUAL. | | | PLEASE CONTACT STEPHEN HUNTER WWITH THE UTILITIES DEPT. | | | AT 561-822-2242. | | | 4) SUBMIT TWO COPIES OF THE REQUIRED BACKFLOW | | | PREVENTION DEVICES IF REQUIRED BY UTILITIES. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|