| Plan Review Notes For Permit 16090010 |
| Permit Number |
16090010 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-06 06:26:28 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE CLARIFY MAIN BREAKER SIZE AS #3 CONDUCTOR IS | | | UNDERSIZED FOR A 125AMP PANELBOARD. IF 100AMP MCB IS | | | EXISTING SHOW ON PLANS. NEC 310.15B16 | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|