| 2016-09-09 08:22:40 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME |
| | JOB ADDRESS: 349 RILYN DR. |
| | DESCRIPTION: UPDATING DRAWING |
| | MASTER PERMIT: 16090003 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | 1. MARK ON THE PLANS THE SCOPE OF WORK AND THE AREA OF |
| | WORK. |
| | 2. YOUR APPLICATION SAYS ?UPDATING DRAWING? UPDATING |
| | WHAT AS THIS IS THE FIRST PRESENTATION FOR THIS |
| | APPLICATION? |
| | 3. YOUR INITIAL PERMIT 15091354 WAS ISSUED W/O |
| | ELECTRIC; YOU LATER SUBMITTED A REVISION 16020955 WHICH |
| | IS CLOSED. THE MASTER PERMIT IS ACTIVE BUT HAS NOT HAD |
| | ANY ELECTRICAL INSPECTIONS. |
| | 4. YOU SHALL SUBMIT A SITE PLAN INDICATING THE LOCATION |
| | OF THE ELECTRIC UTILITY SERVICE POLE WITH RELATION TO |
| | THE ELECTRIC METER AND ALL MAINS AND SUB PANELS. |
| | 5. MINIMUM RACEWAY FOR THE FEEDER TO THE NEW SUBPANEL |
| | IS 1 ??. YOU SHALL INDICATE TYPE OF RACEWAY. |
| | 6. YOU SHALL LABEL EVERY ROOM TO PROPERLY ASCERTAIN ITS |
| | ELECTRICAL REQUIREMENTS. |
| | 7. FBC-RE3602.2/NEC 220.82 SERVICE LOAD: THE MINIMUM |
| | LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND SERVICE |
| | DEVICES THAT SERVE 100 PERCENT OF THE DWELLING UNIT |
| | LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE |
| | E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE |
| | DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE |
| | DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR |
| | FEEDERS IN ACCORDANCE WITH CHAPTER 37. THIS CALCULATION |
| | SHALL BE INDICATED FOR THE ENTIRE SERVICE AND SHOWN ON |
| | THE PLANS. |
| | 8. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A |
| | PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING |
| | THE SPECIFIC PURPOSE OF EVERY CIRCUIT. THIS SHALL BE |
| | SHOWN ON THE PLANS FOR EVERY PANEL. |
| | 9. ON THE PLANS YOU INDICATE A 125 AMP NEW ADDITION |
| | WHICH ALREADY APPEARS ON THE MASTER PERMIT PLANS LOAD |
| | BUT NOT INDICATED ON THE FLOOR PLAN. NOW THERE IS A NEW |
| | 60 AMP PANEL SHOWN BUT NOT CLEARLY IDENTIFIED. |
| | |
| | 10. FBC-RE3903.2/NEC 210.70(A) HABITABLE ROOMS: AT |
| | LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET SHALL |
| | BE INSTALLED IN EVERY HABITABLE ROOM AND BATHROOM. THIS |
| | APPLIES FOR EVERY ROOM BUT IT IS NOT INDICATED FOR THE |
| | ROOM BETWEEN THE KITCHEN AND THE LAUNDRY AREA ON THE |
| | PLANS. |
| | |
| | 11. FBC-RE3902.12/NEC 210.12B ARC-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION: ALL BRANCH CIRCUITS |
| | THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | OUTLETS INSTALLED IN FAMILY ROOMS, DINING ROOMS, LIVING |
| | ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS AND SIMILAR ROOMS |
| | OR AREAS SHALL BE PROTECTED BY A COMBINATION TYPE |
| | ARC-FAULT CIRCUIT INTERRUPTER INSTALLED TO PROVIDE |
| | PROTECTION OF THE BRANCH CIRCUIT. THIS APPLIES TO ALL |
| | NEWLY INSTALLED CIRCUITS. |
| | 12. FBC-R4002.14 NEC 406.12 TAMPER-RESISTANT |
| | RECEPTACLES IN DWELLING UNITS. IN ALL AREAS SPECIFIED |
| | IN 210.52, ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES |
| | SHALL BE LISTED TAMPER RESISTANT RECEPTACLES. THIS |
| | APPLIES TO EVERY RECEPTACLE THAT IS INSTALLED OR |
| | REPLACED. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |