| 2016-11-23 06:54:02 | 1) COMBUSTION AIR CALCULATIONS ARE ALSO REQUIRED FOR | | | THE FUTURE DRYER AT THIS TIME TO ENSURE CODE | | | COMPLIANCE. 2014 FBCR SEC.G2407.9.3.1. | | | 2) THE SHUTOOF VALE FOR THE FUTURE GAS OUTLETS SHALL BE | | | LOCATED AHEAD OF THE REGULATOR. THE PLAN SHOWS THE | | | SHUTOFF VALVE DOWNSTREAM OF THE REGULATOR.THIS CAN BE | | | NOTED. ON THE PLANS IN PEN. 2014 FBCR G2420.4. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|