| Plan Review Notes For Permit 16081314 |
| Permit Number |
16081314 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-06 10:04:37 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16081314 | | | 9/6/16 | | | | | | 1) PROVIDE A NARRATIVE FROM THE DESIGN PROFESSIONALS | | | ITEMIZING ALL CHANGES MADE TO THE APPROVED DRAWINGS | | | SINCE THE LAST APPROVED REVISION #16060333 SUBMITTED ON | | | 6/7/16. IT APPEARS THAT SOME OF THE RTU'S HAVE BEEN | | | RELOCATED AND NEW GRID CEILINGS ARE NOW SHOWN IN THE | | | SHOWROOM ARREA. PLEASE NOTE THAT ALL OF THE DUCTWORK | | | AND DUCT SIZES MUST BE SHOWN ON THE PLANS INCLUDING THE | | | MAIN TRUNKS WHICH ARE NOT SHOWN IN THIS NEW REVISION. | | | ADDITIONALLY I AM SEEING THAT SOME OF THE FLEX DUCT | | | SIZES ARE NOT SHOWN IN THE SALES WORKROOM AND IN THE | | | ADJOINING ROOMS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|