| 2016-09-01 08:55:57 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 16081272 |
| | W. P. B. PERMIT: 15031312 |
| | ADD: 333 FERN ST. |
| | CONT: KAST CONSTRUCTION |
| | CONTACT : |
| | TEL: (561)689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS |
| | ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: SEPT. 01/2016 |
| | ACTION: DENIED |
| | KAST SUBMITTAL# SHOP 226 |
| | |
| | 1) THE SUBMITTAL FOR THE USE OF SHEETROCK BRAND |
| | ACOUSTICAL SEALANT LIST VARIOUS UL SYSTEMS FOR |
| | CONVENTIONAL WALL AND SHAFT WALL DESIGNS. THE 1ST |
| | CONVENTIONAL WALL DESGIN UL LISTING HW-D-0001 THE JOINT |
| | SYSTEM SHOWN AS 3A DOES NOT LIST THIS PRODUCT AS AN |
| | APPROVED JOINT FORMING MATERIAL. |
| | |
| | 2010 FBC-B 714.3.1 THROUGH PENETRATIONS. THROUGH |
| | PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS SHALL |
| | COMPLY WITH SECTION 714.3.1.1 OR 714.3.1.2. |
| | |
| | EXCEPTION: WHERE THE PENETRATING ITEMS ARE STEEL, |
| | FERROUS OR COPPER PIPES, TUBES OR CONDUITS, THE ANNULAR |
| | SPACE BETWEEN THE PENETRATING ITEM AND THE |
| | FIRE-RESISTANCE-RATED WALL IS PERMITTED TO BE PROTECTED |
| | AS FOLLOWS: |
| | |
| | 1. IN CONCRETE OR MASONRY WALLS WHERE THE PENETRATING |
| | ITEM IS A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER AND |
| | THE AREA OF THE OPENING THROUGH THE WALL DOES NOT |
| | EXCEED 144 SQUARE INCHES (0.0929 M2), CONCRETE, GROUT |
| | OR MORTAR IS PERMITTED WHERE IT IS INSTALLED THE FULL |
| | THICKNESS OF THE WALL OR THE THICKNESS REQUIRED TO |
| | MAINTAIN THE FIRE-RESISTANCE RATING; OR |
| | |
| | 2. THE MATERIAL USED TO FILL THE ANNULAR SPACE SHALL |
| | PREVENT THE PASSAGE OF FLAME AND HOT GASES SUFFICIENT |
| | TO IGNITE COTTON WASTE WHEN SUBJECTED TO ASTM E 119 OR |
| | UL 263 TIME-TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM |
| | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| | OF WATER AT THE LOCATION OF THE PENETRATION FOR THE |
| | TIME PERIOD EQUIVALENT TO THE FIRE-RESISTANCE RATING OF |
| | THE CONSTRUCTION PENETRATED. |
| | |
| | 714.3.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN |
| | APPROVED FIRERESISTANCE-RATED ASSEMBLY. |
| | |
| | 714.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH |
| | PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| | PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| | ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| | OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| | THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| | PENETRATED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |